Table 33 TB2 Terminal Designations (1 Relay and 2 Transistor Outputs: IR2T)<br />
Related<br />
Relay Out Terminal Name Description<br />
Param<br />
R0NO Relay 0 N.O. Relay contact output<br />
10<br />
R0NO<br />
R0C<br />
R0NC<br />
R0C<br />
R0NC<br />
Relay 0 Common<br />
Relay 0 N.C.<br />
Rating: 240V AC or 24V DC = 2 A max.<br />
Inductive/Resistive<br />
T0<br />
TC T0 Transistor Output 0 Transistor output<br />
20<br />
T1<br />
TC Transistor Output<br />
Common<br />
Rating: 24V DC = 1 A max.<br />
Resistive<br />
T1 Transistor Output 1 30<br />
Parameter Access<br />
Refer to Select A Device on page 96 for instructions on how to access<br />
parameters on an option module.<br />
Table 34 I/O Module Parameter List By Number<br />
Number Parameter Name Group Number Parameter Name Group<br />
1 Dig In Sts Digital Inputs 56 Anlg In0 Filt BW Analog Inputs<br />
2 Dig In Filt Mask (1)<br />
Digital Inputs 60 Anlg In1 Value Analog Inputs<br />
3 Dig In Filt (1)<br />
Digital Inputs 61 Anlg In1 Hi Analog Inputs<br />
5 Dig Out Sts Digital Outputs 62 Anlg In1 Lo Analog Inputs<br />
6 Dig Out Invert Digital Outputs 63 Anlg In1 LssActn Analog Inputs<br />
7 Dig Out Setpoint Digital Outputs 64 Anlg In1 Raw Val Analog Inputs<br />
10 RO0 Sel Digital Outputs 65 Anlg In1 Filt Gn Analog Inputs<br />
11 RO0 Level Sel Digital Outputs 66 Anlg In1 Filt BW Analog Inputs<br />
12 RO0 Level Digital Outputs 70 Anlg Out Type Analog Outputs<br />
13 RO0 Level CmpSts Digital Outputs 71 Anlg Out Abs Analog Outputs<br />
14 RO0 On Time Digital Outputs 75 Anlg Out0 Sel Analog Outputs<br />
15 RO0 Off Time Digital Outputs 76 Anlg Out0 Stpt Analog Outputs<br />
20 RO1 Sel (2)<br />
Digital Outputs 77 Anlg Out0 Data Analog Outputs<br />
TO0 Sel (3)<br />
Digital Outputs 78 Anlg Out0 DataHi Analog Outputs<br />
21 RO1 Level Sel (2)<br />
Digital Outputs 79 Anlg Out0 DataLo Analog Outputs<br />
TO0 Level Sel (3)<br />
Digital Outputs 80 Anlg Out0 Hi Analog Outputs<br />
22 RO1 Level (2)<br />
Digital Outputs 81 Anlg Out0 Lo Analog Outputs<br />
TO0 Level (3)<br />
Digital Outputs 82 Anlg Out0 Val Analog Outputs<br />
23 RO1 Level CmpSts (2) Digital Outputs 85 Anlg Out1 Sel Analog Outputs<br />
TO0 Level CmpSts (3) Digital Outputs 86 Anlg Out1 Stpt Analog Outputs<br />
24 RO1 On Time (2) Digital Outputs 87 Anlg Out1 Data Analog Outputs<br />
TO0 On Time (3) Digital Outputs 88 Anlg Out1 DataHi Analog Outputs<br />
25 RO1 Off Time (2) Digital Outputs 89 Anlg Out1 DataLo Analog Outputs<br />
TO0 Off Time (3) Digital Outputs 90 Anlg Out1 Hi Analog Outputs<br />
30 TO1 Sel (3) Digital Outputs 91 Anlg Out1 Lo Analog Outputs<br />
31 TO1 Level Sel (3) Digital Outputs 92 Anlg Out1 Val Analog Outputs<br />
32 TO1 Level (3) Digital Outputs 99 PredMaint Sts Predictive Main<br />
33 TO1 Level CmpSts (3) Digital Outputs 100 RO0 Load Type Predictive Main<br />
34 TO1 On Time (3) Digital Outputs 101 RO0 Load Amps Predictive Main<br />
35 TO1 Off Time (3) Digital Outputs 102 RO0 TotalLife Predictive Main<br />
40 PTC Cfg Motor PTC 103 RO0 ElapsedLife Predictive Main<br />
41 PTC Sts Motor PTC 104 RO0 RemainLife Predictive Main<br />
42 PTC Raw Value Motor PTC 105 RO0 LifeEvntLvl Predictive Main<br />
45 Anlg In Type Analog Inputs 106 RO0 LifeEvntActn Predictive Main<br />
46 Anlg In Sqrt Analog Inputs 110 RO1 Load Type (2) Predictive Main<br />
47 Anlg In Loss Sts Analog Inputs 111 RO1 Load Amps (2) Predictive Main<br />
50 Anlg In0 Value Analog Inputs 112 RO1 TotalLife (2)<br />
Predictive Main<br />
<strong>PowerFlex</strong> 750-Series <strong>Install</strong>ation Instructions – Publication 750-IN001C-EN-P – September 2009