Event<br />
Fault Configuration Auto<br />
No. Fault/Alarm Text Type Action Parameter Reset Description/Action(s)<br />
264 Port 4 Checksum Resettable Coast A option module storage checksum failed.<br />
265 Port 5 Checksum Fault<br />
Option data has been set to default values.<br />
266 Port 6 Checksum<br />
267 Port 7 Checksum<br />
268 Port 8 Checksum<br />
269 Port 9 Checksum<br />
270 Port10 Checksum<br />
271 Port11 Checksum<br />
272 Port12 Checksum<br />
273 Port13 Checksum<br />
274 Port14 Checksum<br />
291 HS Fan Life Configurable P493<br />
Predictive maintenance function has reached the event level.<br />
[HSFan EventActn] Perform maintenance.<br />
292 In Fan Life Configurable P500<br />
[InFan EventActn]<br />
293 MtrBrng Life Configurable P506<br />
[MtrBrngEventActn]<br />
294 MtrBrng Lube Configurable P510<br />
[MtrLubeEventActn]<br />
295 MachBrng Life Configurable P515<br />
[MtrBrngEventActn]<br />
296 MachBrng Lube Configurable P519<br />
[MchLubeEventActn]<br />
307 Port7InvalidCard Non-Reset<br />
Fault<br />
Coast Option not valid in that port. Remove option module.<br />
308 Port8InvalidCard Non-Reset<br />
Fault<br />
Coast<br />
313 ENet Checksum Resettable Coast Ethernet/IP storage checksum failed. Data set to default<br />
Fault<br />
values.<br />
314 DLX Checksum Resettable Coast DeviceLogix storage checksum failed. Data set to default<br />
Fault<br />
values.<br />
14037 Net IO Timeout Configurable P52<br />
[DLX Prog Cond]<br />
DeviceLogix has been disabled.<br />
Important: Fault and Alarm event numbers between 3000 and 13999 are generated by a module installed in a<br />
port. Refer to Fault and Alarm Display Codes on page 98 for an explanation.<br />
<strong>Manual</strong>ly Clearing Faults<br />
Refer to the following publications for detailed fault and alarm information.<br />
Event Number Range Publication Title Publication Number<br />
3000…12999 <strong>PowerFlex</strong> 750-Series AC Drives User <strong>Manual</strong> 750-UM001<br />
13000…13999 <strong>PowerFlex</strong> <strong>755</strong> Drive Embedded EtherNet/IP<br />
Adapter User <strong>Manual</strong><br />
750COM-UM001<br />
Step Key(s)<br />
1. Press the “Clear” soft key to acknowledge the fault. The fault information will be<br />
removed so that you can use the HIM.<br />
CLR<br />
2. Address the condition that caused the fault.<br />
The cause must be corrected before the fault can be cleared.<br />
3. After corrective action has been taken, clear the fault by one of these methods:<br />
Press Stop (if running the drive will stop)<br />
Cycle drive power<br />
Select the “Clear” soft key on the HIM Diagnostic folder Faults menu.<br />
<strong>PowerFlex</strong> 750-Series <strong>Install</strong>ation Instructions – Publication 750-IN001C-EN-P – September 2009