Voltage Tolerance<br />

Nominal Line Nominal Motor Drive Full Power Drive Operating<br />

Drive Rating Voltage Voltage Range<br />

Range<br />

380…400 380 380 380…528 342…528<br />

400 400 400…528<br />

480 460 460…528<br />

Drive Full Power Range = Nominal Motor Voltage to Drive Rated Voltage + 10%.<br />

Rated current is available across the entire Drive Full Power Range<br />

Drive Operating Range = Lowest Nominal Motor Voltage - 10% to Drive Rated Voltage + 10%.<br />

Drive Output is linearly derated when Actual Line Voltage is less than<br />

the Nominal Motor Voltage<br />

Hp @ Motor (Drive Output)<br />

Example:<br />

No Drive<br />

Output<br />

Nominal Motor Voltage -10%<br />

Nominal Motor Voltage<br />

Calculate the maximum power of a 5 Hp, 460V motor connected to a 480V<br />

rated drive supplied with 342V Actual Line Voltage input.<br />

Actual Line Voltage / Nominal Motor Voltage = 74.3%<br />

74.3% × 5 Hp = 3.7 Hp<br />

74.3% × 60 Hz = 44.6 Hz<br />

Derated Power Range<br />

Full Power Range<br />

Drive Operating Range<br />

Actual Line Voltage (Drive Input)<br />

Drive Rated Voltage<br />

Drive Rated Voltage +10%<br />

At 342V Actual Line Voltage, the maximum power the 5 Hp, 460V motor<br />

can produce is 3.7 Hp at 44.6 Hz.<br />

Hp @ Motor (Drive Output)<br />

5 Hp<br />

3.7 Hp<br />

No Drive<br />

Output<br />

342V<br />

480V<br />

460V<br />

Actual Line Voltage (Drive Input)<br />