07.08.2013 Views

PowerFlex 755 Install Manual.pdf

PowerFlex 755 Install Manual.pdf

PowerFlex 755 Install Manual.pdf

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

6<br />

CE Conformity<br />

Compliance with the Low Voltage Directive and Electromagnetic<br />

Compatibility Directive has been demonstrated using harmonized European<br />

Norm (EN) standards published in the Official Journal of the European<br />

Communities. <strong>PowerFlex</strong> 750-Series drives comply with the EN standards<br />

listed below when installed according to this <strong>PowerFlex</strong> 750-Series AC<br />

Drive <strong>Install</strong>ation Instructions and the <strong>PowerFlex</strong> 750-Series AC Drive User<br />

<strong>Manual</strong>.<br />

CE Declarations of Conformity are available online at:<br />

www.rockwellautomation.com/products/certification/<br />

Low Voltage Directive (2006/95/EC)<br />

EN 61800-5-1 Adjustable speed electrical power drive systems – Part<br />

5-1: Safety requirements – Electrical, thermal and energy.<br />

EMC Directive (2004/108/EC)<br />

EN 61800-3 Adjustable speed electrical power drive systems – Part 3:<br />

EMC product standard including specific test methods.<br />

General Considerations<br />

For CE compliance, drives must satisfy installation requirements related<br />

to both EN 61800-5-1 and EN 61800-3 provided in this document.<br />

<strong>PowerFlex</strong> 750-Series AC Drives comply with the EMC requirements of<br />

EN 61800-3 when installed according to good EMC practices and the<br />

instructions provided in this document. However, many factors can<br />

influence the EMC compliance of an entire machine or installation, and<br />

compliance of the drive itself does not ensure compliance of all<br />

applications.<br />

<strong>PowerFlex</strong> 750-Series drives are not intended to be used on public<br />

low-voltage networks which supply domestic premises. Without<br />

additional mitigation, radio frequency interference is expected if used on<br />

such a network. The installer is responsible to take measures such as<br />

supplementary line filters and enclosures to prevent interference, in<br />

addition to the installation requirements of this document.<br />

Requirements for supplementary mitigation related to specific high<br />

frequency emission limits are provided in Table 1.<br />

<strong>PowerFlex</strong> 750-Series <strong>Install</strong>ation Instructions – Publication 750-IN001C-EN-P – September 2009

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!