Safe Torque Off Option Module<br />

20-750-S<br />

The safe torque off option is just one component in a safety control system.<br />

Components in the system must be chosen and applied appropriately to<br />

achieve the desired level of operational safety. For detailed information on<br />

applying this option, refer to the <strong>PowerFlex</strong> 750-Series Safe Torque Off<br />

User <strong>Manual</strong>, publication 750-UM002.<br />

Table 35 TB2 Terminal Designations<br />

SP+<br />

SE+<br />

Sd<br />

SP-<br />

SE-<br />

Sd<br />

<strong>Install</strong>ation Notes<br />

Terminal Name Description<br />

SP+ +24 Volt Safety Power User-supplied 24 volt power.<br />

SP- Safety Power Common<br />

45 mA typical<br />

SE+ +24 Volt Safety Enable User-supplied 24 volt power.<br />

SE- Safety Enable Common<br />

25 mA typical<br />

Sd Shield Terminating point for wire shields when an<br />

Sd Shield<br />

EMC plate or conduit box is not installed.<br />

Safety Input Connection Example<br />

Power Supply<br />

Common<br />

SP-<br />

+24V<br />

SP+<br />

1. Ensure the safety enable jumper (J2 SAFETY) is removed.<br />

2. Ensure the hardware enable jumper (J1 ENABLE) is installed. If not<br />

installed, the drive will fault when a start command is issued.<br />

<strong>PowerFlex</strong> 750-Series <strong>Install</strong>ation Instructions – Publication 750-IN001C-EN-P – September 2009<br />

SE-<br />

SE+<br />

Sd Sd<br />

Common<br />

+24V<br />