I/O Wiring Examples<br />

51 Anlg In0 Hi Analog Inputs 113 RO1 ElapsedLife (2)<br />

Predictive Main<br />

52 Anlg In0 Lo Analog Inputs 114 RO1 RemainLife (2)<br />

Predictive Main<br />

53 Anlg In0 LssActn Analog Inputs 115 RO1 LifeEvntLvl (2)<br />

Predictive Main<br />

54 Anlg In0 Raw Val Analog Inputs 116 RO1 LifeEvntActn (2)<br />

Number Parameter Name Group Number Parameter Name Group<br />

Predictive Main<br />

55 Anlg In0 Filt Gn Analog Inputs<br />

(1) Parameter applies to models C-2R and C-1R2T only.<br />

(2) Parameter applies to models C-2R and D-2R only.<br />

(3) Parameter applies to model C-1R2T only.<br />

753 Main Control Board TB1 Wiring Examples<br />

Input/Output Connection Example Required Parameter Changes<br />

Potentiometer Unipolar<br />

Speed Reference<br />

10k Ohm Pot.<br />

Recommended<br />

(2k Ohm Minimum)<br />

Analog Input Bipolar<br />

Speed Reference<br />

±10V Input<br />

Analog Voltage Input<br />

Unipolar Speed<br />

Reference<br />

0 to +10V Input<br />

J4<br />

3 1<br />

4 2<br />

Common<br />

+<br />

Common<br />

+<br />

10VC<br />

+10V<br />

Ai0–<br />

Ai0+<br />

Ai0–<br />

Ai0+<br />

Ai0–<br />

Ai0+<br />

Set Direction Mode<br />

Port 0: P308 [Direction Mode] = 0 “Unipolar”<br />

Set Selection<br />

Port 0: P545 [Spd Ref A Sel] = Port 0: P260 [Anlg In0 Value]<br />

Adjust Scaling<br />

Port 0: P261 [Anlg In0 Hi] = 10 Volt<br />

Port 0: P262 [Anlg In0 Lo] = 0 Volt<br />

Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz<br />

Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz<br />

View Results<br />

Port 0: P260 [Anlg In0 Value]<br />

Port 0: P592 [Selected Spd Ref]<br />

Set Direction Mode<br />

Port 0: P308 [Direction Mode] = 1 “Bipolar”<br />

Set Selection<br />

Port 0: P545 [Spd Ref A Sel] = Port 0: P260 [Anlg In0 Value]<br />

Adjust Scaling<br />

Port 0: P261 [Anlg In0 Hi] = +10 Volt<br />

Port 0: P262 [Anlg In0 Lo] = -10 Volt<br />

Port 0: P547 [Spd Ref A AnlgHi] = +60 Hz<br />

Port 0: P548 [Spd Ref A AnlgLo] = -60 Hz<br />

View Results<br />

Port 0: P260 [Anlg In0 Value]<br />

Port 0: P592 [Selected Spd Ref]<br />

Set Direction Mode<br />

Port 0: P308 [Direction Mode] = 0 “Unipolar”<br />

Set Selection<br />

Port 0: P545 [Spd Ref A Sel] = Port 0: P260 [Anlg In0 Value]<br />

Adjust Scaling<br />

Port 0: P261 [Anlg In0 Hi] = 10 Volt<br />

Port 0: P262 [Anlg In0 Lo] = 0 Volt<br />

Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz<br />

Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz<br />

View Results<br />

Port 0: P260 [Anlg In0 Value]<br />

Port 0: P592 [Selected Spd Ref]<br />