<strong>On</strong>-Board W <strong>Module</strong> <strong>Programming</strong> <strong>and</strong> <strong>Operation</strong><br />
CTI-CRYOGENICS<br />
HELIX TECHNOLOGY CORPORATION<br />
Table B-1: <strong>On</strong>-Board <strong>Module</strong> RS-232 Comm<strong>and</strong>s (Continued)<br />
Comm<strong>and</strong> Parameter Description<br />
T<br />
[1-2] {0-8,ABCF]<br />
[4 digit number]<br />
{| {[?] [0,1,2,8]}<br />
This comm<strong>and</strong> programs the setpoint relays. The first parameter<br />
tells the relay number (1 or 2). The second parameter is one<br />
of two forms. The first, used for setting the item to be programmed,<br />
consists of a selector (0,1,4-8). This form is followed<br />
by a third parameter, a 4 four digit number, if the selector<br />
is 0 - 8. The A - F selectors do not require a following numeric<br />
parameter, as they are logical function settings.<br />
The second form is used to query the settings <strong>and</strong> consists of<br />
the "?" comm<strong>and</strong> element followed by a selector (0-2, 8) to<br />
indicate what data is being queried.<br />
Selector meaning for first form:<br />
0 = Set first stage LL (deg Kelvin)<br />
1 = Set first stage UL<br />
4 = Set Pump TC LL (microns)<br />
5 = Set Pump TC UL<br />
6 = Set AUX TC LL (microns)<br />
7 = Set AUX TC UL<br />
8 = Set time relay (0-9999 seconds)<br />
A = Set unconditional ON<br />
B = Set unconditional OFF<br />
C = Set as REGEN status tracking relay<br />
D = Set as rough valve tracking relay<br />
F = Set as pump motor ON/OFF status tracking relay<br />
Selector meaning for second form:<br />
0:=Query previously set LL (meaning depends upon previous use)<br />
1:=Query previously set UL (meaning depends upon previous use)<br />
2:=Query last sent first form selector (0,1,4-8) used to<br />
establish particular relay function<br />
8:=Query relay time delay (0-9999 seconds)<br />
Example: "$T 1 8 30" /*Set relay time delay to 30 seconds*/<br />
VA [?] Read pump serial number.<br />
Y ? Read elapsed time. The units are in hours <strong>and</strong> expressed as an<br />
integer. The range is up to 65,000 hours.<br />
Z [?] Read the number of REGEN cycles that have been completed.<br />
P/N 8040365 B-9