(1) Set Operation (SETO)<br />
This command is to write operation conditions into the nonvolatile memories in the reader. The new setting<br />
shall be enabled at the upcoming startup.<br />
Command SETO(S)Param1=Value1<br />
Response<br />
Note:<br />
・ Putting equal between a single setting item and a setting value specifies the<br />
value (no need to put ‘-‘ before setting item).<br />
・ Multiple setting items can not be applicable.<br />
SETO[RC]<br />
[RC]: Response Code<br />
*(S) Space Character<br />
Example 1) When the Response I/F after command execution is set RS-232C:<br />
[Tx] SETO rif=2<br />
[Rx] SETO0000<br />
Example 2) When the executed command at the start up is set as [“RDID -ant 122322 -tmo 100”]:<br />
[Tx] SETO iec=1 "RDID -ant 122322 -tmo 100"<br />
[Rx] SETO0000<br />
Example 3) When Input 1 function setting is set as [Command execution, start up edge, "RDID -ant 122322 -<br />
tmo 100"] :<br />
[Tx] SETO in1=1 0 "RDID -ant 122322 -tmo 100"<br />
[Rx] SETO0000<br />
Example 4) When output 3 function setting is set as [Signal is on for 2 seconds] when the executed command<br />
is finished normally, the read data is 12bytes(24characters) and the 5 th to 8 th data is “0000”:<br />
[Tx] SETO ot3=31 2000 dat==****0000****************<br />
[Rx] SETO0000<br />
Example 5) When output 4 function setting is set as[Signal is on for 1 second] if tag count is 10 or less:<br />
[Tx] SETO ot4=31 1000 TCT