Emergency Light Power Supply Unit<br />
Series N 12...<br />
Application:<br />
As power supply for light fittings with up<br />
to 200W which are installed separately<br />
from the "N"-device in a different room.<br />
It is especially recommended in cases in<br />
which the existing environmental conditions<br />
prohibit the use of fittings with selfcontained<br />
battery sets.<br />
Mechanical design:<br />
Housing: Polycarbonate, grey (RAL<br />
9006), cover screwed to the housing.<br />
Battery and electronic device:<br />
Each in a separate housing acc. to DIN<br />
EN 50272-2. Battery compartment with<br />
aeration opening<br />
Mounting: Direct wall mounting (borings<br />
of Ø 6,0mm)<br />
Installation: Plug-type terminals (up to<br />
2,5mm 2 )<br />
Admissible ambient temperature:<br />
-5°C up to +35°C<br />
Insulation class: I<br />
Attention: Installation of this power supply unit is allowed<br />
outside the hazardous area only. Distance between<br />
the light fitting and the "N" unit: 500m<br />
max.Voltage drop to be considered acc. to VDE 0100.<br />
Wiring diagrams for electronic ballast types:<br />
Electrical design:<br />
Emergency power supply unit with battery<br />
for operating 1 or 2 fluorescent light<br />
fittings with electronic ballast (EVG).<br />
Emergency light electronic device with<br />
deep discharge protection and switchover<br />
system for mains/emergency operation.<br />
Automatical monitoring acc. to<br />
EN 62034. The consumer loads will be<br />
monitored by a self- adjusting performance<br />
control device. Manual actuation<br />
of the functional tests and display of<br />
messages and malfunctions via a combined<br />
foil touch screen.<br />
Interface for remote controlling the operating<br />
state via external switch. Interface<br />
for malfunction indication.<br />
Battery set: With maintenance-free leadbattery<br />
Close-down connection<br />
Modes of operation:<br />
Maintained or stand-by operation<br />
Maintained operation: Switching to battery<br />
operation in case of mains failure.<br />
Stand-by operation: Emergency lamp<br />
switches on in case of mains failure only.<br />
Rated voltage: 230V / 50Hz<br />
Suitable for:<br />
Light fittings for fluorescent tubes with<br />
EVG: For double lamp fittings with double<br />
EVG, please consider double consumption<br />
or use fittings with 2 EVG<br />
(separating the systems)<br />
Note:<br />
The EVG in the light fittings connected<br />
to the power supply unit must be suitable<br />
for DC and AC operation.<br />
Light fittings for incandescent lamps.<br />
Admissible consumption acc. to the admissible<br />
consumption of the fluorescent<br />
tubes.<br />
mains<br />
unswitched<br />
mains<br />
switched<br />
ligh fittings<br />
output interface<br />
control input<br />
stand by<br />
N 12...<br />
with separate housing each for the inverter and for the battery set<br />
IP54<br />
inverter<br />
IP32<br />
batterie set<br />
N12/... 18Ah<br />
N12/... 45Ah<br />
Type Article no. Lamps/ Flux factor Weight<br />
W approx.% 1) appr. kg 2<br />
for light fittings with electronic ballast<br />
N12/118-<strong>58</strong>/12/1 DC 12000 0050 1 x 18 – <strong>58</strong> W 1 100 7,1<br />
N12/218-36/18/1 DC 12000 0051 2 x 18 – 36 W 1 100 8,8<br />
N12/2<strong>58</strong>/24/1 DC 12000 0052 2 x <strong>58</strong> W 1 100 12,8<br />
N12/118-<strong>58</strong>/45/3 DC 12000 0053 1 x 18 – <strong>58</strong> W 3 100 19,2<br />
N12/218-36/45/3 DC 12000 0054 2 x 18 – 36 W 3 100 19,2<br />
N12/2<strong>58</strong>/90/3 DC 12000 0055 2 x <strong>58</strong> W 3 100 35,5<br />
1) Ratio effective flux/rated lamp flux 2) Weights without packing material<br />
N12/... 12/24Ah<br />
N12/... 90Ah<br />