for greater distances between lift stations while minimizing the number of lift stations<br />

and the depth of gravity sewers.<br />

Wet well dimensions will vary with each lift/pump station and with the phase of<br />

construction being considered. The diameter of the wet well must accommodate the<br />

number of pumps needed to handle the design flow while maintaining adequate clearance<br />

between each pump. Wet well volume is a function of flow rate and pump cycle time.<br />

Minimum allowable cycle time is 6 minutes from start to start. The size of pumps<br />

required varies from ~2 hp to ~45 hp.<br />

Due to the distance between the service area and the source of wastewater treatment, a<br />

pump station and force main will be needed to serve Area I. The flows for the pump/ lift<br />

station for Area I vary substantially from initial to ultimate conditions. This station<br />

should be designed with two pumps for the initial conditions and will ultimately require<br />

three pumps to meet future conditions. The wet well should be large enough to allow for<br />

a third pump to be added as future demands warrant it. At that time, two pumps will<br />

handle the design flow, and the third will operate as a backup.<br />

The lift stations, which are significantly smaller than the pump station, reqmre<br />

installation of only two pumps for operation. Lift station pumps should be selected such<br />

that a single pump can handle the design flow allowing the second pump to serve as<br />

backup. The lift stations for Area 2 and 3 should be designed to transition from initial to<br />

ultimate flows, if necessary, by pump modifications.<br />

WATER DISTRIBUTION SYSTEM<br />

In addition to hydraulic and pressure considerations, the following design criteria was<br />

applied to sizing the water distribution system.<br />

Diameter<br />

4-inch<br />

Design Limitations<br />

Only on dead-end lines within cui-de-sacs supplying maxrmum of I6<br />

connections.<br />

<strong>Four</strong> <strong>Corner</strong>s Area <strong>Water</strong> and Wastewater Facilities Planning Study<br />

Page 5-4<br />

FINAL REPORT<br />

Revised 2/10/99

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!