SECTION 3.0: DEMAND ESTIMATION<br />

Supply schemes and networks are to be adequately designed or dimensioned to meet initial and growth of consumer<br />

individual and group maximum demand.<br />

The demand estimates are based upon load declared by consumer and TNB’s own information on load profile<br />

characteristics for various consumer classes. Range of values are given as demand profile are known to varies according<br />

to geographical location of consumers around the TNB service areas in Peninsular Malaysia.<br />

Fairly accurate assessment of individual and group demand of consumers are critical for correct dimensioning of network<br />

or facilities in meeting the initial and future demand of consumers as imposed on the network.<br />

3.1 Demand Estimates For Consumer Sub-Classes Or Premises<br />

Table 3-1 and 3-2 indicates the typical ranges of maximum demand for domestic and shop-lots or shop-houses respectively.<br />

These values shall be subjected to revisions based upon of latest results load profiling studies.<br />

Table 3-1: Range of maximum demand (M.D) for domestic consumer sub-classes or premises<br />

No:<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Type Of Premises<br />

Low cost flats, single storey<br />

terrace<br />

Double storey terrace or<br />

apartment<br />

Single storey, semidetached<br />

Single storey bungalow &<br />

three-room condominium<br />

Double storey bungalow &<br />

luxury condominium<br />

Minimum<br />

(kW)<br />

Average<br />

(kW)<br />

Maximum<br />

(kW)<br />

1.5 2.0 3.0<br />

3.0 4.0 5.0<br />

3.0 5.0 7.0<br />

5 7.0 10<br />

8.0 12 15<br />

Table 3-2: Range of maximum demand (M.D) for types of shop-houses<br />

No:<br />

Type Of Premises<br />

Minimum<br />

(kW)<br />

Average<br />

(kW)<br />

Maximum<br />

(kW)<br />

1 Single storey shop house 5 10 15<br />

3 Double storey shop house 15 20 25<br />

3 Three storey shop house 20 30 35<br />

4 Four storey shop house 25 35 45<br />

5 Five storey shop house 30 40 55<br />

42 TENAGA<br />