SECTION 4: SUPPLY SCHEMES<br />
Based upon consumer declared demand level and required security level, supply schemes to consumers are appropriately<br />
designed to meet these requirements and planning criteria as discussed in section 2.<br />
4.1 Maximum Demand Levels And Supply Schemes<br />
The table below indicates the typical schemes for various demand levels of individual consumers. In the case of<br />
maximum demand (M.D) ranges of 5MVA to 10MVA, the supply voltage options of either 11kV or 33kV will ultimately<br />
be determined by the predominant supply voltage where the prospective consumer is to be connected.<br />
Consumers with M.D approaching 1000kVA have the option of taking supply at 11kV.<br />
Table 4-1: Typical supply schemes for various M.D levels<br />
M.D ranges of individual<br />
consumer<br />
Supply<br />
voltage<br />
Typical supply scheme<br />
Up to 12 KVA 240V Overhead services from LV mains.<br />
12kVA to 100kVA<br />
100kVA to 1000kVA<br />
1000kVA to 5000kVA<br />
1000kVA to 10000kVA<br />
5000kVA to 25000kVA<br />
Above 25000kVA<br />
415V<br />
415V<br />
11kV<br />
22kV<br />
33kV<br />
132kV ,<br />
275 kV<br />
Three phase overhead or underground<br />
cable service from existing LV mains.<br />
Direct cable service from LV board from<br />
a sub-station<br />
Directly fed through TNB 11kV switching<br />
station<br />
Directly fed through TNB 22kV switching<br />
station<br />
Directly fed through TNB 33kV switching<br />
station<br />
Directly fed through TNB 132kV and<br />
275kV switching station respectively<br />
4.2 Substation Categories, Type & Design<br />
4.2.1 Sub-station categories<br />
a. Transmission Main Intake (Pencawang Masuk Utama-PMU)<br />
Transmission Main Intake is the interconnection point of 132kV or 275kV to the distribution network. The standard<br />
transmission capacity and voltage transformation provided at the PMU are as follows:-<br />