6.4 Metering Cubicle<br />

The consumer shall provide an appropriate metering cubicle to specifications stated in Appendix 19. The maximum<br />

distance allowable between the metering CTs and the metering cubicle is shown in Table 3. The consumer shall send the<br />

cubicle to TNB Metering Services HQ/Regional office for wiring up.<br />

Table 3<br />

CT Burden<br />

(VA)<br />

15<br />

15<br />

30<br />

30<br />

30<br />

30<br />

Secondary Rate Current<br />

(Amps)<br />

5<br />

5<br />

5<br />

5<br />

1<br />

1<br />

Cross Connection Of<br />

Conductor<br />

(mm 2 )<br />

2.5<br />

4.0<br />

2.5<br />

4.0<br />

2.5<br />

4.0<br />

Maximum Distance<br />

Allowable<br />

(m)<br />

30<br />

47<br />

65<br />

100<br />

1,647<br />

2,545<br />

Where meter burden for current circuit = 0.5 VA/ph<br />

6.5 Location of Metering Cubicle<br />

An enclosed locked room specifically for the purpose of installing the floor mounted metering cubicle shall be provided.<br />

The minimum area shall be 1.5 m by 1.7 m.<br />

6.6 Power Supply Point for Remote Meter Reading<br />

A 13 Amps Switch Socket Outlet (S.S.O) is to be provided and shall be installed at the top of metering cubicle.<br />

6.7 Cable Requirement<br />

6.7.1 Indoor Breakers<br />

The consumer shall provide and connect a 12-core PVC/SWA/PVC of 2.5mm 2 or higher between the consumer high<br />

voltage switchboard and the metering cubicle. There shall be no intermediary joint.<br />

The armoured cable shall not be buried or enclosed. Preferably it shall be laid on cable tray.<br />