Oil and gas production handbook An introduction to oil ... - ABB Group
Oil and gas production handbook An introduction to oil ... - ABB Group
Oil and gas production handbook An introduction to oil ... - ABB Group
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
PSD <strong>and</strong> can be h<strong>and</strong>led with less strict requirements.<br />
These actions are h<strong>and</strong>led by the emergency shut down system (ESD) <strong>and</strong><br />
process shut down system (PSD) according <strong>to</strong> functional safety<br />
requirements <strong>and</strong> st<strong>and</strong>ards. Thus, a typical ESD function might require a<br />
SIL 3 or even SIL 4 level, while PSD loops could be SIL 2 or SIL 3.<br />
Smaller ESD systems, e.g., on wellhead platforms, can be hydraulic or<br />
hardwired (non-programmable).<br />
8.1.3 Fire <strong>and</strong> <strong>gas</strong> system<br />
The fire <strong>and</strong> <strong>gas</strong> system is not generally<br />
related <strong>to</strong> any particular process.<br />
Instead, it divides in<strong>to</strong> fire areas by<br />
geographical location. Each fire area<br />
should be designed <strong>to</strong> be self-contained,<br />
in that it should detect fire <strong>and</strong> <strong>gas</strong> by<br />
several types of sensors, <strong>and</strong> control fire<br />
protection <strong>and</strong> firefighting devices <strong>to</strong><br />
contain <strong>and</strong> fight fire within the fire area.<br />
In the event of fire, the area will be<br />
partially shut off through closure of<br />
ventilation fire dampers. A fire area<br />
protection data sheet typically shows what detection exists for each fire area,<br />
<strong>and</strong> which fire protection action should be taken in case of an incident.<br />
The type <strong>and</strong> number of the detection, protection <strong>and</strong> fighting devices<br />
depends on the type of equipment <strong>and</strong> size of the fire area <strong>and</strong> will vary for<br />
different process areas, e.g., electrical rooms <strong>and</strong> accommodation rooms.<br />
Fire detection:<br />
• Gas detection: Combustible <strong>and</strong> <strong>to</strong>xic <strong>gas</strong>, electro-catalytic or<br />
optical (IR) detec<strong>to</strong>r<br />
• Flame detection: Ultraviolet (UV) or infra red (IR) optical detec<strong>to</strong>rs<br />
• Fire detection: Heat <strong>and</strong> ionic smoke detec<strong>to</strong>rs<br />
• Manual pushbut<strong>to</strong>ns<br />
Firefighting, protection:<br />
• Gas-based firefighting, such as CO 2<br />
• Foam-based firefighting<br />
• Water-based firefighting: sprinklers, mist (water spray) <strong>and</strong> deluge<br />
• Protection: Interface <strong>to</strong> emergency shutdown <strong>and</strong> HVAC fire dampers.<br />
107