Job Specification<br />

For<br />

Silencer<br />

DOCUMENT No.<br />

A307-16-46-SP-6519<br />

Rev. A<br />

Page 2 of 5<br />

1.0 GENERAL<br />

1.1 This specification outlines the minimum requirements for complete design,<br />

engineering, manufacturing, procurement of raw materials and bought out<br />

components, assembly at shop, inspection, testing, painting, packing and delivery of<br />

the Silencers for UNIT- DHDT& VGU-HDT of M/s BPCL, IREP-KOCHI.<br />

1.2 This job specification provides the additional requirements along with the requirements<br />

of standard specification 6-12-0030.<br />

2.0 SCOPE<br />

2.1.1 Scope of Supply<br />

Supply of following Silencers as per enclosed Data Sheets, P&ID’s, this job<br />

specification, and other specifications, documents of Material Requisition.<br />

i. IG-LZ-105 Steam generator silencer-1- Qty-1<br />

ii. IG-LZ-106 Steam generator silencer-1 - Qty-1<br />

iii. IG-LZ-116 LP Steam Desuperheater 1 Silencer - Qty-1<br />

iv. IV-LZ-211 LP Steam Vent Silencer- Qty-1<br />

v. IV-LZ-212 MP Steam Vent Silencer- Qty-1<br />

vi. IV-LZ-213 LP Steam Vent Silencer - Qty-1<br />

vii. IV-LZ-214 LP Steam Vent Silencer- Qty-1<br />

2.1.2 The silencer shall be supplied complete with:<br />

- Acoustic insulation.<br />

- Detachable rain hood & bird screen.<br />

- Drain connection with 3/4" Gate valve for draining the condensate<br />

- Support brackets along with anchor bolts.<br />

- Lifting lugs.<br />

- Painting material.<br />

- Insulation cleats.<br />

- Documents as called for in Vendor Data Requirement.<br />

- Bolts, Nuts & gaskets for all bolted connections.<br />

- Spares (Refer clause no. 7.0 of this specification)<br />

- IBR approval for item IV-LZ-212<br />

2.2 Scope of Services<br />

- Design and engineering.<br />

- Manufacture, inspection & testing as per Cl.5.5.<br />

- Surface preparation, shop primer/ painting & finish painting.<br />

- Packing for transportation to site.<br />

- Performance testing.<br />

2.3 Exclusions:<br />

- Civil & Structural Works<br />

- Erection & Installation of equipment<br />

3.0 CODES AND STANDARDS<br />

3.1 Following codes, standards and recommended practices shall be followed to the<br />

extent applicable:<br />

Format No. <strong>EIL</strong> 1641-1924 Rev. 1<br />

Page 183 of 291<br />

Copyright <strong>EIL</strong> – All rights reserved

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!