JOB SPECIFICATION<br />
FOR SURFACE PREPARATION<br />
AND PROTECTIVE COATING<br />
JOB SPECIFICATION No.<br />
A307-000-06-42-PLS-01<br />
Rev.0<br />
PAGE 28 OF 49<br />
TABLE 12.0<br />
EXTERNAL COATING SYSTEMS FOR UNINSULATED CARBON STEEL<br />
AND LOW ALLOY STEEL STORAGE TANKS (For all plant locations, coastal<br />
or inland)<br />
Sl.<br />
No.<br />
12.1<br />
Design Temp.<br />
in o C<br />
All Process Units & Off-sites<br />
Surface<br />
Preparation<br />
(Field)<br />
Primer<br />
Coating system (Field)<br />
(see note 1 below)<br />
Finish Coat<br />
Total<br />
DFT<br />
in<br />
Microns<br />
(min.)<br />
Remarks<br />
All external surfaces of shell, wind girders, appurtenances, roof tops of all above ground tank including top<br />
side of external and internal floating roof and associated external structural works.<br />
12.1.1 -14 to 80<br />
SSPC-SP-10<br />
1coat of F-9 @ 65-75µ<br />
DFT/coat + 1coat of P-6<br />
@ 40µ DFT/ coat ;<br />
2 coats of F-6A @<br />
100µ DFT /coat + 1<br />
coat of F-2 @ 40µ<br />
DFT/ coat;<br />
345-355<br />
F-6 should<br />
be suitable<br />
for<br />
occasional<br />
water<br />
immersion<br />
12.1.2 81 to 150<br />
SSPC-SP-10<br />
1 coat of F-15 primer @<br />
80µ DFT/ coat + 1 coat<br />
of F-15 intermediate<br />
coat @ 80µ DFT/coat ;<br />
1 coat of F-15 finish<br />
coat @80µ DFT/ coat +<br />
1coat of F-2 @ 40µ<br />
DFT/ coat;<br />
280 -<br />
12.1.3 151 to 500 SSPC-SP-10<br />
1coat of F-9 @ 65-75µ<br />
DFT/coat<br />
2 coats of F-12 @20 µ<br />
DFT/ coat<br />
Or<br />
1 coat of F-16 @ 50 µ<br />
DFT / coat<br />
105<br />
or<br />
115<br />
-<br />
12.2 External surfaces of bottom plate (soil side) for all storage tanks.<br />
12.2.1 -14 to 80<br />
12.2.2 81 to 150<br />
SSPC-SP-10<br />
SSPC-SP-10<br />
12.2.3 151 to 550 SSPC-SP-10<br />
1 coat of F-9 @<br />
65-75µ DFT/ coat<br />
1 coat of F-15 primer @<br />
80µ DFT/ coat + 1 coat<br />
of F-15 intermediate<br />
coat @ 80µ DFT/coat ;<br />
(80+80=160)<br />
1 coat of F-16 @ 125 µ<br />
DFT /coat<br />
3 coats of F-7@ 100µ<br />
DFT/coat (3x100=300)<br />
1 coat of F-15 finish<br />
coat @ 80µ DFT/ coat<br />
1 coat of F-16 @ 125 µ<br />
DFT /coat<br />
365-375<br />
F-7 should<br />
be suitable<br />
for<br />
immersion<br />
service of<br />
the<br />
products<br />
given<br />
240 -<br />
250 -<br />
12.3 For underside of the bottom plate (in case tank is not lifted during PWHT) (see Note 2c)<br />
Format No. 8-00-0001-F1 Rev. 0<br />
Copyright <strong>EIL</strong> – All rights reserved<br />
Page 267 of 291