JOB SPECIFICATION<br />

FOR SURFACE PREPARATION<br />

AND PROTECTIVE COATING<br />

JOB SPECIFICATION No.<br />

A307-000-06-42-PLS-01<br />

Rev.0<br />

PAGE 40 OF 49<br />

19.3 Colour Bands<br />

Location of colour bands:<br />

At Battery Limits<br />

Intersection points & change of direction points in piping<br />

Midway of piping section, near valves, across culverts<br />

At 50 M interval on long stretch pipes<br />

At starting and termination points.<br />

Minimum width:<br />

NB<br />

Width<br />

3” and below 75 mm<br />

Above 3” to 6”<br />

NB X 25 MM<br />

Above 6” to 12” NB X 18 MM<br />

Above 12”<br />

NB X 15 MM<br />

!!! Note:<br />

For insulated pipes, NB indicates<br />

OD of the insulation<br />

Sequence :<br />

Colour bands shall be arranged in sequence showing Table above and the sequence follows the<br />

direction of flow. The width of the 1 st Band to 2 nd band is 4:1,<br />

!!! Note : Wherever deemed required by Process Department or Safety, pipes handling hazardous<br />

substances will be given hazard marking of 30 mm wide diagonal stripes of Black and Golden Yellow<br />

as per IS : 2379.<br />

19.4 Special Camouflage Painting for Uninsulated Crude and Product Storage Tanks.<br />

Paint specification shall be as per standards.<br />

Camouflage painting scheme for Defense requirement in irregular patches will be applied with<br />

3 colours<br />

Dark Green : Light green : Medium Brown<br />

5 : 3 : 2<br />

The patches shall be irregular and asymmetrical and inclined at 30 to 60 Degrees.<br />

Patches should be continuous at surface meeting lines / points.<br />

Slits / holes shall be painted in dark green shade.<br />

Width of patches shall be 1 to 2 meters.<br />

19.5 Identification Markings on Equipment / Piping<br />

Equipment tag Numbers shall be Stenciled / neatly painted using normal 'Arial' Lettering<br />

Style on all equipment and piping (Both insulated & uninsulated) after completion of all paint<br />

Format No. 8-00-0001-F1 Rev. 0<br />

Copyright <strong>EIL</strong> – All rights reserved<br />