MECHANICAL DATA SHEET<br />

FOR<br />

SILENCER<br />

DOCUMENT No.<br />

A307-0IG-16-46-DS-4106<br />

Rev. A<br />

Page 3 of 3<br />

3.13 External Insulation (To be provided by others) : Cleats to be provided by vendor.<br />

3.14 Internal & External Painting : Complete primer & painting as per Job<br />

specification A307-000-06-42-PLS-01<br />

*: Data to be furnished after award of order<br />

# REFER PROCESS DATA SHEET (PDS) & P&ID<br />

NOTES<br />

1. Drain connection with a ¾” Gate Valve along with a Blind Flange shall be provided as per enclosed<br />

piping material specification & valve material specification<br />

2. This Mechanical Data sheet to be read in conjunction with process data sheet for item no-IG-<br />

LZ-106 & P&ID A166-LZ-1114<br />

3. Bidder shall submit design calculation for local load analysis due to nozzle loading for diffuser<br />

nozzle as per WRC 107 and ensure that the head / nozzle thicknesses and reinforcement pad<br />

/ insert plate sizes / thicknesses are adequate. The loading shall be as per documents no.<br />

A307-0IG-16-46-ST-0038 attached in this MR. Required reinforcing pad / Insert plate may be<br />

provided to meet the loadings without any implication on price and schedule. The local load<br />

analysis shall be carried out within 1 month of issue of PR, as this involves procurement of<br />

material by Bidder.<br />