A1A - EIL Tender portal
A1A - EIL Tender portal
A1A - EIL Tender portal
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Job Specification<br />
For<br />
Silencer<br />
DOCUMENT No.<br />
A307-16-46-SP-6519<br />
Rev. A<br />
Page 4 of 5<br />
4.11 The size and weight of the equipment shall preferably be kept minimum.<br />
4.12 The silencer shall be provided with lifting lugs for ease of installation at site.<br />
4.13 Allowable loads on Silencer Inlet Nozzle:<br />
Wherever piping is connected directly to silencer nozzles local load analysis<br />
calculations for shell/ head to nozzle junction to be carried-out as per WRC-107.<br />
Allowable loading shall be considered as per doc no- A307-0IG-16-46-ST-0038.<br />
Above loading are maximum. However in some exceptional cases if actual forces and<br />
moment values due to connected piping are more, this will be intimated to vendor<br />
during detail engineering. Vendor shall make necessary changes required for<br />
strengthening the nozzles & the supporting brackets.<br />
4.15 For Inlet Nozzle/ Flange, Drain Nozzle/ Flange: PMS attached in MR to be referred<br />
inline with P&IDs.<br />
For Gate Valve,: VMS attached in MR to be referred inline with P&IDs.<br />
4.16 For IBR Silencer ( IV-LZ-212), approval of drawings, documents, stagewise inspection<br />
and final certification of the equipment by Inspectorate of Boilers shall be included in<br />
bidder’s scope. Complete design of equipment as per IBR shall be carried out by<br />
vendor.<br />
4.17 Bidder to furnish the unit rates for addition/ deletion of the items (support<br />
brackets, nozzles, RF Pad, insert plate, nozzle flanges etc.) as per the doc. No.<br />
A307-16-46-UR-6519 attached with MR. (for changes due to piping loads, over<br />
and above those specified above, etc.).<br />
5.0 INSPECTION AND TESTING<br />
5.1 a) Equipment shall be inspected (stage wise & final) by <strong>EIL</strong>.<br />
b) Quoted prices shall include for the above<br />
5.2 Any or all the test, at purchaser's option shall be witnessed by purchaser / <strong>EIL</strong>.<br />
However, such inspection shall be regarded as check-up and shall in no way absolve<br />
the vendor of his responsibility.<br />
5.3 Testing at Bidder's works shall include but not limited to the following.<br />
Non-destructive tests such as Radiography, Dye Penetration Test etc. shall be<br />
followed for testing the welds. As a minimum all pressure parts of the silencers shall<br />
be spot radiographed as per ASME Code.<br />
All fillet welds shall be DP tested.<br />
5.4 Material certificates shall be furnished at the time of inspection.<br />
5.5 The silencer shall be tested at site for a period of 20 minutes for determining the<br />
guaranteed sound/Noise pressure level as specified in MDS under simulated<br />
operating conditions. The silencer shall be tested at site in the presence of Bidder’s<br />
representative and Bidder’s offer shall be deemed to include the same<br />
Format No. <strong>EIL</strong> 1641-1924 Rev. 1<br />
Page 185 of 291<br />
Copyright <strong>EIL</strong> – All rights reserved