JOB SPECIFICATION<br />

FOR SURFACE PREPARATION<br />

AND PROTECTIVE COATING<br />

JOB SPECIFICATION No.<br />

A307-000-06-42-PLS-01<br />

Rev.0<br />

PAGE 35 OF 49<br />

TABLE 17.0<br />

COATING SYSTEM (INTERNAL PROTECTION) FOR GALVANIZED OR<br />

NON FERROUS OR STAINLESS STEEL/ DUPLEX STAINLESS STEEL<br />

COMPONENTS OF COOLERS/ CONDENSERS FOR FRESH WATER<br />

SERVICE<br />

Sl.<br />

No.<br />

Design<br />

Temp. in o C<br />

Surface Preparation<br />

& Pre-erection/Shop<br />

Primer<br />

17.1 Up to 80 Sweep Blasting<br />

Coating System<br />

(Post-erection / Field)<br />

Primer<br />

1 coat of F-15 @<br />

80µ DFT/coat;<br />

17.2 80 to 140 Sweep Blasting ---<br />

Finish paint<br />

1 coat of F-15 @<br />

80µ DFT/coat;<br />

1 coat of Glass<br />

Fibre Reinforced<br />

Novolac epoxy of<br />

1.5 mm DFT<br />

Total Final<br />

DFT<br />

in Microns<br />

(min.)<br />

Remarks<br />

160 -<br />

1500 -<br />

18.0 STORAGE<br />

18.1 All paints and painting materials shall be stored only in rooms to be arranged by contractor<br />

and approved by Engineer-in-charge for the purpose. All necessary precautions shall be<br />

taken to prevent fire. The storage building shall preferably be separate from adjacent<br />

building. A signboard bearing the word “PAINT STORAGE – NO NAKED LIGHT –<br />

HIGHLY INFLAMABLE” shall be clearly displayed outside. Manufacturer’s<br />

recommendation shall be followed for storage of paint materials.<br />

19.0 COLOUR CODE<br />

The following colour coding system shall be followed. However alternate colour coding may<br />

also be followed as per Owner’s colour coding practice/scheme.<br />

19.1 IDENTIFICATION<br />

The system of colour coding consists of a ground colour and secondary colour bands<br />

superimposed over the ground colour. The ground colour identifies the basic nature of the<br />

service and secondary colour band over the ground colour distinguishes the particular<br />

service. The ground colour shall be applied over the entire length of the un-insulated pipes.<br />

For insulated lines ground colour shall be provided as per specified length and interval to<br />

identify the basic nature of service and secondary colour bands to be painted on these<br />

specified length to identify the particular service. Above colour code is applicable for both<br />

unit and offsite pipelines.<br />

Format No. 8-00-0001-F1 Rev. 0<br />

Copyright <strong>EIL</strong> – All rights reserved<br />

Page 274 of 291

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!