4 Basic planning<br />
10<br />
All the data necessary for the selection and layout of a <strong>Defensor</strong> <strong>Mk5</strong> humidifier system are provided<br />
in the following chapters. The following planning steps are required:<br />
• Selecting the unit (see chapter 4.1)<br />
• Selecting the control system (see chapter 4.2)<br />
• Selecting options (see chapter 4.3)<br />
• Selecting accessories (see chapter 4.4)<br />
4.1 Selecting the unit<br />
The selection of the unit is reflected in the type description:<br />
1. Application<br />
2. Supply water quality<br />
3. Required maximum steam capacity<br />
4. Required heating voltage<br />
1. Application<br />
The type series can be selected on the basis of the following table:<br />
Scope of use Type series<br />
For direct or indirect room air humidification with<br />
standard requirements for control precision.<br />
For direct or indirect room air humidification in<br />
laboratory and process applications where there<br />
are increased requirements for control precision.<br />
Visual<br />
Process<br />
Achievable control precision<br />
– Visual: ±5 %rh (assuming optimum control distance, PI-control and use of untreated water)<br />
±2 %rh (assuming optimum control distance, PI-control and use of fully demineralized water)<br />
– Process: ±2 %rh (assuming optimum control distance, PI-control and use of untreated water)<br />
±1 %rh (assuming optimum control distance, PI-control and use of fully demineralized water)<br />
2. Supply water quality<br />
Description<br />
unit with a lime collector tank for operation with untreated<br />
water and partially softened water.<br />
Unit without a lime collector tank for operation with fully<br />
demineralized water with a conductivity value