4.4.2 Accessory details<br />

Steam distribution pipes 81-... for indirect room humidification<br />

The steam distribution pipes are selected on the basis of the duct width (for horizontal installation) or<br />

the duct height (for vertical installation) and the capacity of the steam humidifier.<br />

Important! Always select the longest possible steam distribution pipe (optimum humidification distance).<br />

L<br />

B<br />

Steam distribution pipes 81-...<br />

for <strong>Defensor</strong> <strong>Mk5</strong> (CrNi steel)<br />

Duct width (B) Steam output<br />

Type Length in mm (L) 3) in mm max. in kg/h<br />

81-200 1) 200 210…400 10<br />

81-350 2) 350 400…600 30<br />

81-500 2) 500 600…750 30<br />

81-650 650 750…900 50<br />

81-800 800 900…1100 50<br />

81-1000 1000 1100…1300 50<br />

81-1200 1200 1300…1600 50<br />

81-1500 1500 1600…2000 50<br />

81-1800 1800 2000…2400 50<br />

81-2000 2000 2200…2600 50<br />

81-2300 2300 2500…2900 50<br />

81-2500 2500 2700…3100 50<br />

1) Only for units with a max. steam capacity of 10 kg/h<br />

2) Only for units with a max. steam capacity of 30 kg/h<br />

3) Special length available on request<br />

Note: If the humidification distance (see chapter 5.3.1) has to be reduced for technical reasons, the<br />

amount of steam per basic unit must be divided between two steam distribution pipes or the OptiSorp<br />

steam distribution system must be used. If this is the case, contact your <strong>Defensor</strong> supplier.<br />

Steam distribution pipe “Process” (accessory “Z...”)<br />

The steam distribution pipe “Process” is used for direct humidification of material in manufacturing<br />

processes (process humidification), or in ventilation ducts with a critical saturation distance (the<br />

steam distribution pipe “Process” reduces the saturation distance by approximately 30%). The desired<br />

length must be specified when ordering.<br />

Please contact your <strong>Defensor</strong> distributor, they will assist you in customizing the steam distribution head<br />

“Process”. Please have the following information readily available:<br />

– steam quantity in kg/h<br />

– dimensions of ventilation duct (width x height)<br />

Important! The table for the determination of the humidification distance provided in chapter 5.3.1 does<br />

not apply to the Process steam distribution pipe.<br />

17