Integr.time[min]<br />

010<br />

softstart<br />

off<br />

softstart time<br />

30 Min<br />

softst. power<br />

50 %<br />

demineral. mode<br />

on<br />

Note: The P-Range is used to smooth the control characteristic. Increasing<br />

the P-Range boosts the smoothing applied to the control characteristic.<br />

However, this causes a permanent deviation, proportional to the bandwidth<br />

of the P-Range.<br />

– Integral time of the internal PI controller<br />

Integral time of the internal PI controller in minutes.<br />

Note: This menu option is available only if the internal PI controller is active.<br />

Factory setting: 10 Minutes<br />

Options: off (000/integral time disabled), 2 - 100 Minutes<br />

Note: The integral time setting determines the period allowed to reach the<br />

nominal humidity. Setting the integral time to the optimal value prevents the<br />

control characteristic from overshooting and, at the same time, balances the<br />

permanent deviation caused by the P-Range value.<br />

– Soft start<br />

Enabling (on) or disabling (off) the Soft start function.<br />

Note: Enable the soft start function if you are using softened water or water with<br />

a high conductivity.<br />

Factory setting: off<br />

Available settings: on (Soft start enabled), off (Soft start disabled)<br />

Note: After restart or after the unit has been idle for 4 hours (stand-by) the Soft<br />

start function reduces the humidification capacity to a preset value for a selectable<br />

period (value settings see parameters below).<br />

– Time limit for Soft start<br />

Select the time limit for the Soft start function in minutes.<br />

Note: This menu item is available only if the Soft start function is enabled.<br />

Factory setting: 30 minutes<br />

Setting range: 1…255 minutes<br />

– Capacity limit for Soft start<br />

Set the capacity limit for the Soft start function in % of maximum humidification<br />

capacity.<br />

Note: This menu item is available only if the Soft start function is enabled.<br />

Factory setting: 50 %<br />

Setting range: 4…100 %<br />

– Demineralization mode<br />

Enabling (“on”) or disabling (“off”) the Demineralization mode.<br />

Note: Enable the demineralization mode if you are using softened water or<br />

water with a high conductivity.<br />

Factory setting: on<br />

Available settings: on (Demineralization mode enabled)<br />

off (Demineralization mode disabled)<br />

Note: The Demineralization mode flushes the steam cylinder within an hour<br />

after a preset number of scum detections has taken place (see next parameter<br />

“Demineralization delay”). This prevents the formation of scum.<br />