power limit [%]<br />
100<br />
46<br />
drain cycle<br />
4: 120<br />
stand-by heating<br />
on<br />
softstart<br />
on<br />
softstart time<br />
30 Min<br />
softst. power<br />
50 %<br />
demineral. mode<br />
on<br />
demineral. delay<br />
3<br />
– Flushing cycle<br />
The following indications are provided for the set flushing interval:<br />
Left: Switch setting on rotary switch “S1”<br />
Right: Set flushing interval<br />
Note: The flushing interval is set on switch “S1” on the control board. Please<br />
observe the notes in chapter 6.1.<br />
– Stand-by heating<br />
Stand-by heating activated (“on”)/deactivated (“off”).<br />
Note: If stand-by heating is active the water temperature in the steam cylinder<br />
is constantly kept at approx. 70 °C. Stand-by heating may be activated/<br />
deactivated with the DIP switch “S4-1” on the control board. Please observe<br />
the information given in chapter 6.1.<br />
– Capacity limitation<br />
The set capacity limitation as a percentage of the maximum capacity.<br />
– Soft start<br />
Soft start enabled (“on”)/disabled (“off”).<br />
Note: After restart or after the unit has been idle for 4 hours (stand-by) the Soft<br />
start function reduces the humidification capacity to a preset value for a selectable<br />
period (value settings see parameters below).<br />
– Time limit for Soft start<br />
Selected time limit for Soft start function in minutes.<br />
Note: This menu item is available only if the Soft start function is enabled.<br />
– Capacity limit for Soft start<br />
Selected capacity limit for Soft start function in % of maximum capacity.<br />
Note: This menu item is available only if the Soft start function is enabled.<br />
– Demineralization mode<br />
Demineralization mode enabled (“on”)/disabled (“off”).<br />
Note: The Demineralization mode flushes the steam cylinder within an hour<br />
after a preset number of scum detections has taken place (see Demineralization<br />
delay). This prevents the formation of scum.<br />
– Demineralization delay<br />
Selected the delay for demineralization.<br />
Note: This menu item is available only if the Demineralization mode is<br />
enabled.<br />
Note: This value determines the number of scum detections allowed (maximum<br />
level in steam cylinder is reached) before the steam cylinder is flushed<br />
for a preset time.