power limit [%]<br />

100<br />

46<br />

drain cycle<br />

4: 120<br />

stand-by heating<br />

on<br />

softstart<br />

on<br />

softstart time<br />

30 Min<br />

softst. power<br />

50 %<br />

demineral. mode<br />

on<br />

demineral. delay<br />

3<br />

– Flushing cycle<br />

The following indications are provided for the set flushing interval:<br />

Left: Switch setting on rotary switch “S1”<br />

Right: Set flushing interval<br />

Note: The flushing interval is set on switch “S1” on the control board. Please<br />

observe the notes in chapter 6.1.<br />

– Stand-by heating<br />

Stand-by heating activated (“on”)/deactivated (“off”).<br />

Note: If stand-by heating is active the water temperature in the steam cylinder<br />

is constantly kept at approx. 70 °C. Stand-by heating may be activated/<br />

deactivated with the DIP switch “S4-1” on the control board. Please observe<br />

the information given in chapter 6.1.<br />

– Capacity limitation<br />

The set capacity limitation as a percentage of the maximum capacity.<br />

– Soft start<br />

Soft start enabled (“on”)/disabled (“off”).<br />

Note: After restart or after the unit has been idle for 4 hours (stand-by) the Soft<br />

start function reduces the humidification capacity to a preset value for a selectable<br />

period (value settings see parameters below).<br />

– Time limit for Soft start<br />

Selected time limit for Soft start function in minutes.<br />

Note: This menu item is available only if the Soft start function is enabled.<br />

– Capacity limit for Soft start<br />

Selected capacity limit for Soft start function in % of maximum capacity.<br />

Note: This menu item is available only if the Soft start function is enabled.<br />

– Demineralization mode<br />

Demineralization mode enabled (“on”)/disabled (“off”).<br />

Note: The Demineralization mode flushes the steam cylinder within an hour<br />

after a preset number of scum detections has taken place (see Demineralization<br />

delay). This prevents the formation of scum.<br />

– Demineralization delay<br />

Selected the delay for demineralization.<br />

Note: This menu item is available only if the Demineralization mode is<br />

enabled.<br />

Note: This value determines the number of scum detections allowed (maximum<br />

level in steam cylinder is reached) before the steam cylinder is flushed<br />

for a preset time.