– System 3: Supply air humidity control<br />

Supply air humidity control (humidity sensor installed in supply air duct) should be used only<br />

where room humidity control is impracticable for technical reasons. Such systems always<br />

require a PI-controller. The humidity sensor (A1) is located in the supply air duct after the steam<br />

distribution pipe.<br />

A1 humidity sensor<br />

B1 B2 <strong>Mk5</strong> B3<br />

B1 ventilation interlock<br />

B2<br />

B3<br />

airflow monitor<br />

safety humidistat<br />

PII<br />

PII PIE Y<br />

internal continuous controller (PI-controller)<br />

external continuous controller (e.g. PI-controller)<br />

input signal from A1<br />

PIE<br />

Which humidity control system for which application?<br />

<strong>Defensor</strong><br />

Application Location of the humidity sensor<br />

Room or exhaust air duct supply air duct<br />

Air conditioning systems with:<br />

supply air portion up to 33% System 1 System 1<br />

supply air portion up to 66% System 1 or 2 System 2 or 3<br />

supply air portion up to 100% System 2 System 3<br />

Supply air humidity control ––– System 3<br />

Direct room humidification System 1 –––<br />

Please contact your <strong>Defensor</strong> supplier, if your application meets the following conditions:<br />

– Humidification of small rooms up to 200 m3 – Air conditioning systems with a high number of air exchanges<br />

– Systems with variable air volume flow<br />

– Test facilities with extreme control accuracy requirements<br />

– Rooms with a high variation in max. steam capacity<br />

– Systems with temperature fluctuations<br />

– Cold rooms and systems with dehumidification<br />