6.5 Setting the operating parameters<br />
48<br />
You can adapt various <strong>Defensor</strong> <strong>Mk5</strong> steam-air humidifier operating parameters to the operating<br />
requirements on the setting level of the control and display unit. The setting level is protected by an<br />
access code to guard against unauthorized access.<br />
Caution! The settings on the setting level have a direct influence on the operating behavior of<br />
the steam-air humidifier. The settings must therefore only be made by personnel who are familiar<br />
with the techniques of humidification and climatic control and with the <strong>Defensor</strong> <strong>Mk5</strong> system.<br />
Overview of the setting level and operation<br />
<strong>Mk5</strong> Visual<br />
ready<br />
and<br />
entry code<br />
8808<br />
adjust level<br />
language<br />
(Enter=Entry)<br />
power limit [%]<br />
(Enter=Entry)<br />
1)<br />
inlet valve cor.<br />
(Enter=Entry)<br />
controller funct<br />
(Enter=Entry)<br />
2)<br />
ref.value rh[%]<br />
(Enter=Entry)<br />
2)<br />
P-band [%]<br />
(Enter=Entry)<br />
2)<br />
integr.time[min]<br />
(Enter=Entry)<br />
Operation: – For call-up of the setting level see the following “Call-up of the setting level”<br />
– Next menu item<br />
– Previous menu item<br />
– For change to set values see the section “Changing the set values”<br />
– Exit the setting level with <br />
Note: 1) appears only on <strong>Mk5</strong> Process units<br />
2) appears only if “controller funct” is activate (“on”)<br />
3) appears only if “softstart” is activate (“on”)<br />
4) appears only if “demineral. mode” is activate (“on”)<br />
5) appears only if “serial interface” is activate (“on”)<br />
Menu<br />
softstart<br />
(Enter=Entry)<br />
3)<br />
softstart time<br />
(Enter=Entry)<br />
3)<br />
softst. power<br />
(Enter=Entry)<br />
demineral. mode<br />
(Enter=Entry)<br />
4)<br />
demineral. delay<br />
(Enter=Entry)<br />
Normal service mode<br />
Setting level<br />
serial interface<br />
(Enter=Entry)<br />
5)<br />
baudrate<br />
(Enter=Entry)<br />
5)<br />
RTS/CTS<br />
(Enter=Entry)<br />
diagnose pgm<br />
(Enter=Entry)<br />
faulthistory<br />
. /. /6.B/6.A<br />
erase history<br />
(Enter=Entry)