6.7.3 Replacing unit fuses<br />

Warning Danger of death! Before replacing the unit fuse the steam humidifier must be<br />

switched off and secured against unintentional reconnection as described in chapter 6.3.<br />

Take care that the electricity supply to the main contactor is disconnected (check with voltage<br />

tester).<br />

Warning! Electronic components are very sensitive to electrostatic discharge. To protect these<br />

components, measures must be taken against damage from electrostatic discharge when<br />

replacing the unit fuse (ESD protection).<br />

The unit fuses may only be replaced by trained and qualified personnel.<br />

Important! If the unit fuse blows this is generally due to a faulty unit component. Therefore you should<br />

check these components before replacing the fuse (see table below).<br />

Only use the correct type of fuse according to the following table.<br />

Warning! It is not permitted to use repaired fuses.<br />

Power board (F1..F3, F1...F6 or F1...F9)<br />

Supply module (F2)<br />

Supply module (F1)<br />

Control board (F5)<br />

Fuse Specification Before replacing, check<br />

F1 on supply module 6.3 A, slow-acting Drain pump (blocked or coil faulty)<br />

F2 on supply module 1 A, quick-acting Inlet valve (blocked or coil faulty)<br />

F5 on control board 50mA, quick-acting Control signal<br />

F1…F3 on power board<br />

(<strong>Mk5</strong> Visual/Process 5-.. and 8-..)<br />

16 A, super quick-acting Heating elements (on short-circuit)<br />

F1…F9 on power board<br />

(all other models)<br />

20 A, super quick-acting Heating elements (on short-circuit)<br />

6.7.4 Resetting fault indication “Error”<br />

In order to return the steam humidifier to operation after fault elimination, the steam humidifier must be<br />

switched off for approx. 5 seconds and then switched on again.<br />