6 Operation<br />

6.1 Unit configuration<br />

40<br />

Warning - danger of electric shock! Disconnect the steam humidifier from the mains<br />

supply (heating and control voltage) before opening the unit.<br />

Warning! Electronic components inside the unit are very susceptible to electrostatic<br />

discharges. For the protection of these components, measures must be taken during all<br />

installation work to prevent damage caused by electrostatic discharge (ESD–protection).<br />

All adjusting elements are situated on the control board:<br />

– Rotary switch “S1”: drain interval<br />

– Rotary switch “S2”: maintenance interval<br />

– Rotary switch “S3”: control signal (see chapter 5.5.3)<br />

– Rotary switch “S4”: unit settings<br />

Setting the drain interval (“S1”)<br />

The evaporation process increases the concentration of mineral salts in the steam cylinder. Periodic<br />

flushing followed by refilling of fresh water can keep the concentration of mineral salts at a low level.<br />

The interval time to be selected depends on the quality of the water and the type of unit. It may have<br />

to be adapted to the actual circumstances during operation. The following maintenance intervals can<br />

be selected.<br />

Position drain interval Unit type <strong>Defensor</strong> <strong>Mk5</strong> Visual/Process<br />

“S1” at 100% steam capacity 5-.. 8-.. 10-.. 16-.. 20-.. 24-.. 30-.. 40-.. 50-.. 60-.. 80-..<br />

0<br />

∞<br />

1 720 min. VE VE VE VE VE VE VE VE VE VE VE<br />

2 360 min.<br />

3 180 min.<br />

4 120 min. X<br />

5 60 min. X X<br />

6 30 min. X<br />

7 20 min. X X<br />

8 10 min. X X X X X<br />

9 5 min.<br />

VE= Setting for fully demineralized water<br />

X= Standard setting<br />

Notes:<br />

– The standard settings (see preceding table) refer to a water hardness of 210 ppm (12 °dH or 21 °fH,<br />

respectively). When using partially softened water the switch must be set to the next lower position<br />

(e.g. from position 5 to position 4).<br />

– If the <strong>Defensor</strong> <strong>Mk5</strong> is operated with fully demineralized water, the switch can be set to “1”.<br />

– If no humidification takes place for more than 4 hours, the unit will proceed to a flushing cycle and<br />

a float test upon the next humidification request.