Defensor Mk5 Technical Documentation
Defensor Mk5 Technical Documentation
Defensor Mk5 Technical Documentation
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
7 <strong>Technical</strong> data<br />
62<br />
<strong>Defensor</strong> <strong>Mk5</strong> Visual/Process<br />
5-.. 8-.. 10-.. 16-.. 20-.. 24-.. 30-.. 40-.. 50-.. 60-.. 80-..<br />
Steam output 0 - 100 % infinitely variable<br />
Number of units 1 1 1 1 1 1 1 1 2 2 2<br />
Steam connection G 1 1/4"<br />
Resolution 1.0 %<br />
Control of steam output<br />
- active 0…20 V (Phase intersect), 0…10 VDC, 1…5 VDC, 0…5 VDC<br />
0…4.25 VDC (Potentiometer), 0…1 VDC, 2…10 VDC<br />
0…20 mADC, 4…20 mADC<br />
- passive all potentiometric humidity sensors from 140 Ω…10 kΩ<br />
- On/Off control Off; ≥2,5 VDC…20 VDC --> On<br />
Duct air pressure Overpressure max. 1500 Pa, Underpressure max. 1000 Pa<br />
(for duct pressures outside these values contact your <strong>Defensor</strong> supplier)<br />
Permissible ambient temperature 1…40 °C<br />
Permissible ambient humidity 1…75 %rh<br />
Water feed<br />
– Connection G 1/2"<br />
– Permissible water pressure 1…10 bar<br />
– Feed temperature 1…40 °C<br />
– Water quality untreated water, fully demineralized water or partially softened water<br />
Water outlet<br />
– Connection Internal-ø= 40 mm<br />
– Outlet temperature max. 90 °C<br />
Weight in kg<br />
– Operation 51 51 52 53 71 73 73 74 1x71 2x73 2x74<br />
1x73<br />
– Net 36 36 37 38 41 43 43 44 1x41 2x43 2x44<br />
1x43<br />
Dimensions in mm<br />
– Height 1087 1087<br />
– Width 500 594<br />
– Depth 437 392<br />
Content of lime collector tank in l 5 10<br />
Test certificate SEV, VDE<br />
Type of protection IP21