Water supply<br />

The water feed pipe (min. internal Ø: 8 mm) is to be connected via the filter valve that is available as<br />

an accessory, to the connection on the unit (see detailed illustration). Alternatively, a shut-off valve and<br />

a water filter may be installed. The installation of the filter valve should be made as close as possible<br />

to the steam humidifier.<br />

Warning - danger of damage! Union nut at the humidifier connection must be hand-tightened<br />

only.<br />

The following connection specifications must be observed:<br />

– Connection on unit: G 1/2" (Union nut)<br />

– Min. inner Ø of supply line: 8 mm<br />

– Admissible mains pressure 1.0 to 10.0 bar (hammer-free system)<br />

For mains pressures >10 bar, connection must be made via pressure reducing valve (adjusted to<br />

2.0 bar). For mains pressures