Defensor Mk5 Technical Documentation
Defensor Mk5 Technical Documentation
Defensor Mk5 Technical Documentation
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Water supply<br />
The water feed pipe (min. internal Ø: 8 mm) is to be connected via the filter valve that is available as<br />
an accessory, to the connection on the unit (see detailed illustration). Alternatively, a shut-off valve and<br />
a water filter may be installed. The installation of the filter valve should be made as close as possible<br />
to the steam humidifier.<br />
Warning - danger of damage! Union nut at the humidifier connection must be hand-tightened<br />
only.<br />
The following connection specifications must be observed:<br />
– Connection on unit: G 1/2" (Union nut)<br />
– Min. inner Ø of supply line: 8 mm<br />
– Admissible mains pressure 1.0 to 10.0 bar (hammer-free system)<br />
For mains pressures >10 bar, connection must be made via pressure reducing valve (adjusted to<br />
2.0 bar). For mains pressures