18<br />
OptiSorp steam distribution system<br />
The OptiSorp steam distribution system is used in ventilation ducts where only a short humidification<br />
distance is available (see chapter 5.3.1 for calculation of humidification distance). Duct dimensions<br />
should be given when ordering. Please note the following data for this:<br />
H<br />
B<br />
OptiSorp Number of max. steam capacity Duct dimension<br />
steam connections in kg/h 1) Width in mm Height in mm<br />
System 1 1 45 (30) 450...2700 450...1650<br />
System 2 2 90 (60) 450...2700 450...2200<br />
1) For duct width