6.16<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

ZONE 1 ZONE 2 ZONE 21 ZONE 22<br />

E X - C O N T R O L U N I T S A N D C O N T R O L S T A T I O N S<br />

Measuring AM72<br />

E X - C O N T R O L S T A T I O N S<br />

I Measuring instrument AM 72 I<br />

Technical data<br />

Measuring instrument AM 72, type 411 82<br />

Marking to 94/9/EC II 2 G ⎮ II 2 D T 48°C<br />

Type of protection EEx e II T6 / EEx e ib IIC T6<br />

EC-Type Examination Certificate PTB 00 ATEX 3117<br />

Degree of protection acc. to EN 60529 IP 66<br />

Movement Moving iron EEx e Moving coil EEx ib IIC<br />

Accuracy Class 2.5 Class 1.5<br />

Overload range 10-fold - 25 sec.<br />

25-fold - 4 sec.<br />

50-fold - 1 sec.<br />

indicated 1:1.5<br />

10-fold - 5 sec.<br />

Measuring ranges n / 1A 0 - 20 mA<br />

0 - 25 A direct 4 - 20 mA<br />

Li: - max. 0.1 mH<br />

Ci: - max. 0,1 nF<br />

Ui: - max. 30 V<br />

Ii: - max. 150 mA<br />

Connection terminals 2 x 1.5 - 4 mm2 Cable entry 1 x M25 (Ø 8 - 17 mm)<br />

Weight approx. 0.70 kg<br />

6.16 CEAG SICHERHEITSTECHNIK GMBH<br />

125<br />

155<br />

5.6<br />

22<br />

85<br />

75<br />

77.5<br />

5<br />

73<br />

73<br />

92<br />

Measuring instrument AM 72<br />

Dimensions in mm