8.18<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

ZONE 1 ZONE 2 ZONE 21 ZONE 22<br />

E X - C O N T R O L A N D D I S T R I B U T I O N S S Y S T E M S<br />

NH-00<br />

E X - B U I L T - I N C O M P O N E N T S<br />

Technical data<br />

NH 00 Main fuse up to 125 A<br />

I NH 00 Main fuse up to 125 A I<br />

Marking to 94/9/EG II 2 G<br />

Type of protection EEx de IIC<br />

EC-type examination certificate PTB 99 ATEX 1066 U<br />

Rated voltage 690 V ⎮ Signal contact max. 250 V<br />

Rated current 2 A to 125 A<br />

Rated switching capacity 100 kA<br />

Terminal cross-section up to 95 mm 2 ⎮ Signal contact 2 x 2.5mm 2<br />

Min. terminal cross-section up to 25 A 4 mm 2 ⎮ up to 35 A 6 mm 2 ⎮ up to 50 A 10 mm 2<br />

Weight approx. 3.5 kg (without fuse)<br />

Singnal contact optional<br />

up to 63 A 25 mm 2 ⎮ up to 100 A 50 mm 2 ⎮ up to 125 A 70 mm 2<br />

Ordering details type: NH 00 3-pole<br />

Equipped without signal contact<br />

Version Rated current Mounting width Order No.<br />

3-pole 2 A - 125 A 150 mm NH0 300 X X<br />

Ordering details type: NH 00 3-pole<br />

Equipped with signal contact (1 changeover)<br />

Version Rated current Mounting width Order No.<br />

3-pole 2 A - 125 A 150 mm NH0 301 X X<br />

XX = Please state required rated current in Amperes.<br />

8.18 CEAG SICHERHEITSTECHNIK GMBH<br />

192<br />

X 170<br />

150<br />

95<br />

8 18.5<br />

6.5<br />

X 125<br />

NH 00<br />

x = mounting dimensions<br />

Dimensions in mm