7.30<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

ZONE 1 ZONE 2 ZONE 21 ZONE 22<br />

E X - S A F E T Y A N D M A I N C U R R E N T S W I T C H E S<br />

GHG 263 1301 R0001<br />

E X - M A I N C U R R E N T S W I T C H E S<br />

Technical data<br />

40 A 3-pole<br />

Marking to 94/9/EC II 2 G ⎮ II 2 D T 53 °C<br />

Type of protection EEx ed ia IIC T6<br />

EC-Type Examination Certificate PTB 99 ATEX 1161<br />

Rated voltage up to 690 V (20 A)<br />

Rated current max. 40 A<br />

Switching capacity AC-3 230 V/40 A 400 V/40 A 500 V/40 A 690 V/32 A<br />

Short-circuit backup fuse max. 80 A (400 V) ⎮ max. 63 A (690 V)<br />

Degree of protectcion acc. to EN 60529 IP 66<br />

Enclosure material Glass-fibre reinforced polyester<br />

Connecting terminals 2 x 16 mm 2<br />

GHG 263 0048 R....<br />

I 40 A I<br />

Cable entry M 25 (Ø 8 - 17 mm) ⎮ M40 (Ø 16 - 28 mm)<br />

Weight approx. 2.3 kg (3-pole version)<br />

approx. 6.5 kg (6-pole version)<br />

Ordering details main current switch 40 A 3-pole<br />

Version Cable entry Type Order No.<br />

0 - I 2 x M40, 1 x M25 ON-OFF switch GHG 263 1301 R0001<br />

0 - Y - D 3 x M40,<br />

2 x M25 screw plug star-delta GHG 263 0048 R0005<br />

0 - I - II 3 x M40,<br />

2 x M25 screw plug Dahlander GHG 263 0048 R0006<br />

Ordering details main current switch 40 A 3-pole<br />

Bestückt with 2 auxiliary contacts, 1 x NO, 1 x NC<br />

Version Cable entry Type Order No.<br />

I - II 3 x M40, 1 x M25,<br />

1 x M25 screw plug change-over switch GHG 263 0048 R0002<br />

I - 0 - II 3 x M40, 1 x M25<br />

1 x M25 screw plug change-over switch GHG 263 0048 R0003<br />

I - 0 - II 2 x M40, 1 x M25<br />

1 x M25 screw plug reversing switch GHG 263 0048 R0004<br />

Customised versions on request.<br />

For fixing materials and accessories, see page 7.44.<br />

7.30 CEAG SICHERHEITSTECHNIK GMBH<br />

225<br />

X197<br />

271<br />

X 247<br />

Ø 12<br />

Ø 7<br />

7<br />

8<br />

140<br />

X 123-126<br />

156<br />

GHG 263 1301 R0001<br />

271<br />

X 247<br />

275<br />

211<br />

11<br />

GHG 263 0048 R....<br />

Dimensions in mm