U <<br />

145<br />

105.5<br />

Manual motor starter 25 A<br />

I ><br />

I ><br />

I ><br />

110.4<br />

D1 D2 ND PE D 1 3 5 14 22 13 21 2 4 6<br />

(12) (11)<br />

ZONE 1 ZONE 2 ZONE 21 ZONE 22<br />

E X - C O N T R O L A N D D I S T R I B U T I O N S S Y S T E M S<br />

Technical data<br />

Manual motor starter 0.1 A to 25 A<br />

Marking to 94/9/EG II 2 G<br />

Type of protection EEx de IIC<br />

EC-type examination certificate PTB 99 ATEX 1007 U<br />

Manual motor starter<br />

E X - B U I L T - I N C O M P O N E N T S<br />

I Manual motor starter 0.1 A to 25 A I<br />

Rated voltage 690 V, 50/60 Hz, 440 V DC<br />

Auxiliary contact Optional<br />

Rated voltage 110 V, 230 V, 400 V and 500 V 50/60 Hz<br />

Short-circuit backup fuse not required<br />

Terminal cross-section 2 x (0.75 to 2.5) mm 2<br />

Rated current max. 25 A<br />

Rated switching capacity AC-3 25 A<br />

Thermal tripping characteristic T II<br />

Tripping time at 6x le ≥ 5 Second<br />

Terminal cross-section 2 x (0.75 to 4.0) mm 2<br />

Weight 1.3 kg<br />

Ordering details type: 3-pole,<br />

Equipped without auxiliary contact, without undervoltage trip<br />

Version Rated current Mounting width Order No.<br />

3-pole 0.1 A - 25 A 106 mm MSS 3HU X X<br />

H = 0 without auxiliary contact<br />

H = 1 with auxiliary contact (1 NO + 1 NC)<br />

U = 0 without undervoltage trip<br />

U = 5 with undervoltage trip<br />

Short-circuit protection up to 100 kA and<br />

max. back-up fuse protection<br />

Setting range 230 V AC 400 V AC 500 V AC 690 V AC Temp.<br />

lcs gl, aM lcs gl, aM lcs gl, aM lcs gl, aM<br />

0.1 A ... 0.16 A T6<br />

1.0 A ... 1.6 A T6<br />

1.6 A ... 2.5 A short-circuit proof, 40 25 T6<br />

2.5 A ... 4.0 A no back-up fuse 40 35/40 10 40 T6<br />

4.0 A ... 6.3 A required 30 50 3 40 T6<br />

6.3 A ... 9.0 A 30 80 3 50 T6<br />

9.0 A ... 12.5 A 50 80 20 80 3 50 T6<br />

12.5 A ... 16.0 A 50 100 20 100 3 50 T6<br />

16.0 A ... 20.0 A 50 100 20 100 2 50 T5<br />

20.0 A ... 25.0 A 50 125 50 125 20 125 2 50 T5<br />