MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />

Subpart L Fire Protection<br />

75.1100-1 Type <strong>and</strong> Quality of Firefighting Equipment<br />

Waterlines, with hoses attached, shall be of sufficient size<br />

to deliver 50 gallons of water per minute at a nozzle pressure<br />

of 50 psig. With this water flow <strong>and</strong> nozzle pressure, an<br />

effective solid stream can be projected about 60 feet in a 6foot<br />

high entry. Water flow through the nozzle can be<br />

measured by a pitot tube instrument if the diameter of the<br />

nozzle orifice is known. For adjustable nozzles, the rate of<br />

flow decreases as the water flow pattern changes from a solid<br />

stream to a spray or fog. The minimum rate of 50 gpm shall be<br />

available at the most distant point in the mine. The type <strong>and</strong><br />

method of installation of waterlines are options of the<br />

operator, provided they meet the requirements of Subpart L.<br />

Portable water cars shall be examined during each regular<br />

inspection to ensure that the pump, valves <strong>and</strong> fittings have<br />

not corroded excessively.<br />

A portable chemical car shall contain 125 pounds of allpurpose<br />

dry powder for each 500 gallons of water capacity<br />

required of a water car. The car shall contain provisions for<br />

expelling dry chemical through a hose <strong>and</strong> attached nozzle.<br />

The hose shall be a minimum of 100 feet long <strong>and</strong> a maximum of<br />

150 feet long. The dry chemical is expelled rapidly;<br />

therefore, firefighting operations using a portable chemical<br />

car should be conducted by personnel trained in its use.<br />

The portable foam-generating machine or device shall be<br />

equipped with all hardware necessary to install the machine or<br />

device in a mine passageway. Generally, plastic brattice (or<br />

equivalent) material is needed to seal the entry at the<br />

installation location. The foaming agent tends to be<br />

corrosive to metal parts <strong>and</strong>, unless the machine or device is<br />

carefully cleaned after use, the valves, pump <strong>and</strong> fittings may<br />

become inoperative.<br />

Only foam-producing <strong>and</strong> multi-purpose dry chemical portable<br />

fire extinguishers are acceptable. The older type sodium<br />

bicarbonate extinguisher can be converted for use with allpurpose<br />

dry chemicals; however, such conversion can be<br />

hazardous <strong>and</strong> voids the approval of Underwriters'<br />

Laboratories, Inc., <strong>and</strong> Factory Mutual Research Corp.<br />

Therefore, such converted extinguishers are not acceptable as<br />

complying with paragraph (e) of this Section.<br />

Portable fire extinguishers purchased after March 30, 1971, shall<br />

February 2003 (Release V-33) 91