MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />

When emergency material is stored at a central warehouse or<br />

building supply company, the inspector should determine whether<br />

the material will be available for shipment to the mine at all<br />

times.<br />

75.1100-3 Condition <strong>and</strong> Examination of Firefighting Equipment<br />

All firefighting equipment shall be maintained in a usable <strong>and</strong><br />

operative condition. Rock dust shall be dry, water cars shall be<br />

kept filled <strong>and</strong> operative, water containers <strong>and</strong> pails shall be in<br />

usable condition, <strong>and</strong> chemical extinguishers shall be examined<br />

every 6 months. The inspection of chemical extinguishers should<br />

determine that:<br />

1. The extinguisher is in its designated place.<br />

2. Access <strong>and</strong> visibility to the extinguisher are not<br />

obstructed.<br />

3. Seals should not be broken. This is an indication that<br />

the extinguisher may not be full. Some extinguishers have<br />

to be lifted slightly to determine if they are full.<br />

4. The extinguisher has not been physically damaged or have<br />

any obvious defects (clogged nozzle, corrosion, leakage,<br />

damaged hose, etc.).<br />

5. The examination record on the tag is up-to-date. This<br />

section is interpreted to mean that water shall be kept<br />

constantly in the waterlines in sufficient amounts to meet<br />

the requirements of Section 75.1100-1(a). The phrase "50<br />

gallons of water per minute," as used in Section 75.1100-<br />

1(a), does not mean for only 1 minute.<br />

In those instances where there is danger of freezing <strong>and</strong> bursting<br />

the waterlines if water is kept in the lines, the mine operator<br />

should consider a pressurized system, or should file a petition<br />

for modification under the provisions of Section 101(c) of the<br />

Act.<br />

75.1101 Deluge-Type Water Sprays, Foam Generators; Main <strong>and</strong><br />

Secondary Belt-Conveyor Drives<br />

In requiring fire suppression systems for belt conveyor drives,<br />

apply the same rule used in Section 75.603 <strong>and</strong> in Section 75.1103,<br />

which permit the use of belt conveyor drives without a fire<br />

suppression system for 24 production shift hours after they have<br />

been installed before a citation is issued.<br />

October 2003 (Release V-34) 97