05.06.2013 Views

Program Policy Manual - VOLUME V - Mine Safety and Health ...

Program Policy Manual - VOLUME V - Mine Safety and Health ...

Program Policy Manual - VOLUME V - Mine Safety and Health ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />

the phase-to-neutral voltage for potential relaying.<br />

Where an ungrounded high-voltage circuit is accepted for use<br />

underground under the provisions of Section 75.802(b), the circuit<br />

must be provided with grounded-phase protection.<br />

Grounded-phase indicating lights that do not trip the circuit<br />

breaker upon the occurrence of a phase-to-ground fault are not<br />

acceptable as compliance with this Section.<br />

Short-circuit protection can be provided by using the<br />

instantaneous units of overcurrent relays or by using inverse-time<br />

overcurrent relays with minimal time dial settings.<br />

The pickup of the instantaneous unit of an overcurrent relay is<br />

independent of the pickup of the inverse-time unit <strong>and</strong> is<br />

determined by the position of the top of the screw on the<br />

instantaneous unit.<br />

Overcurrent devices are required in at least two phases of threephase<br />

high-voltage underground distribution circuits.<br />

75.800-3 Testing, Examination, <strong>and</strong> Maintenance of Circuit<br />

Breakers; Procedures<br />

If the circuit breaker located on the surface provides overload,<br />

short-circuit, undervoltage, <strong>and</strong> grounded-phase protection for the<br />

entire underground circuit, only that circuit breaker is required<br />

to be tested by this Section. Circuit breakers installed<br />

underground for coordination purposes in such circuits are not<br />

required to be tested; however, each independent ground- check<br />

circuit must be tested in accordance with this Section.<br />

The tests required by paragraph (b)(2) of this Section may be<br />

conducted one of three ways:<br />

1. Primary injection test. This test method involves<br />

sufficient current to cause the circuit breaker to trip<br />

through at least two current transformers associated with<br />

the circuit breaker. Since this method requires that test<br />

connections be made on high-voltage conductors or<br />

terminals, stringent safety procedures must be followed.<br />

This method simultaneously tests the current transformer<br />

ratio, the current transformer secondary wiring, the<br />

operation <strong>and</strong> calibration of the relays, <strong>and</strong> the operation<br />

of the circuit breaker tripping circuit.<br />

February 2003 (Release V-33) 75

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!