MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />
Subpart H Grounding<br />
75.701 Grounding Metallic Frames, Casings, <strong>and</strong> Other<br />
Enclosures of Electric Equipment<br />
When a three-phase resistance grounded system supplies power to a<br />
rectifier bridge <strong>and</strong> to other portable or mobile loads, neither<br />
the positive nor negative conductor of the direct-current circuit<br />
can be grounded. The frames of the direct-current equipment must<br />
be grounded to the alternating-current ground rectifier frame.<br />
However, when a power system is being designed so as to provide a<br />
separate bank of transformers to supply power to the rectifier<br />
bridge <strong>and</strong> a separate bank of transformers to supply power to the<br />
a.c. portable or mobile loads, then one polarity of the rectifier<br />
bridge can be grounded. All frames of direct-current equipment<br />
are then grounded to the grounded power conductor.<br />
75.702 Protection Other Than Grounding<br />
Portable tools protected by an approved system of double<br />
insulation, or its equivalent, need not be grounded. Where such<br />
an approved system is employed, the tool will be distinctly<br />
marked.<br />
75.703 Grounding Off-Track Direct-Current Machines <strong>and</strong><br />
Enclosures of Related Detached Components<br />
"Related detached components" refers to associated parts such as<br />
contactor compartments, control switches, or rheostats that are<br />
not installed on the frame of the machine. The metal frames or<br />
enclosures of such components shall be connected to the same<br />
grounding medium as the main frame of the machine to which it is<br />
related.<br />
Metal frames or housings of pumps, battery chargers, sequence <strong>and</strong><br />
slippage switches, breaker boxes, remote control switches,<br />
rheostats, rock-dusting machines, auxiliary fans, belt drives,<br />
belt feeders, contactor compartments, <strong>and</strong> any other equipment or<br />
devices receiving power from direct-current power systems shall be<br />
grounded to the grounding medium of the power system feeding such<br />
equipment or devices. The grounding medium for d.c. systems is<br />
normally the mine track or grounded d.c. feeder. When ungrounded<br />
d.c. systems are used, the grounding medium is usually the<br />
grounded frame of the rectifier or generator.<br />
The metal battery case of batteries being charged shall be<br />
grounded. In instances where batteries are being charged without<br />
removing them from mobile equipment, the frame of the machine or<br />
battery case shall be grounded to the grounded frame of the<br />
charger to prevent the machine from becoming "alive" through<br />
failure of insulation in the charger, such as between primary <strong>and</strong><br />
February 2003 (Release V-33) 72