Program Policy Manual - VOLUME V - Mine Safety and Health ...
Program Policy Manual - VOLUME V - Mine Safety and Health ...
Program Policy Manual - VOLUME V - Mine Safety and Health ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />
Subpart J Underground Low- <strong>and</strong> Medium-Voltage Alternating Current<br />
Circuits<br />
75.900 Low- <strong>and</strong> Medium-Voltage Circuits Serving<br />
Three-Phase Alternating Current Equipment;<br />
Circuit Breakers<br />
Each of the four protective features required by this Section must<br />
be provided for all underground low- <strong>and</strong> medium-voltage three-phase<br />
a.c. circuits with the exception of trailing cables, which must have<br />
short-circuit, undervoltage, <strong>and</strong> grounded-phase protection. Circuit<br />
breakers providing short-circuit protection for trailing cables<br />
shall be adjusted so as not to exceed the maximum allowable<br />
instantaneous settings specified under Section 75.601-1. Shortcircuit<br />
<strong>and</strong> overcurrent protection for circuits shall conform to the<br />
National Electrical Code, 1968. Charts listing sizes <strong>and</strong> proper<br />
overload <strong>and</strong> short-circuit protection for motors <strong>and</strong> motor circuit<br />
conductors can be found in Appendix E of this volume. These tables<br />
shall be used to determine compliance with this Section.<br />
"Adequate interrupting capacity" is the ability of a circuit breaker<br />
to safely interrupt the maximum amount of current that can flow<br />
through its contacts upon occurrence of a short circuit at any point<br />
in the circuit without damage to itself.<br />
Low- <strong>and</strong> medium-voltage three-phase circuits used underground shall<br />
be protected against the harmful effects of a grounded phase in any<br />
circuit connected to the same transformer secondary. Consequently,<br />
if one bank of transformers supplies power to both underground <strong>and</strong><br />
surface loads, both the surface <strong>and</strong> underground portions of the<br />
circuit(s) shall be provided with grounded-phase protection.<br />
Grounded-phase protective devices for resistance-grounded circuits<br />
should be adjusted to operate on as low a value of fault current as<br />
practical, preferably not more than 50 percent of the current rating<br />
of the neutral grounding resistor.<br />
75.901 Protection of Low- <strong>and</strong> Medium-Voltage Three-Phase<br />
Circuits Used Underground<br />
When two phase conductors of a three-phase resistance grounded<br />
circuit are used to power single-phase loads, the equipment frames<br />
must be grounded to the grounded side of the grounding resistor.<br />
The grounding circuit shall be provided with a ground check circuit<br />
as required by Section 75.902 <strong>and</strong> the circuit shall be protected in<br />
accordance with the requirements of Section 75.900.<br />
February 2003 (Release V-33) 81