05.06.2013 Views

Program Policy Manual - VOLUME V - Mine Safety and Health ...

Program Policy Manual - VOLUME V - Mine Safety and Health ...

Program Policy Manual - VOLUME V - Mine Safety and Health ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />

Subpart J Underground Low- <strong>and</strong> Medium-Voltage Alternating Current<br />

Circuits<br />

75.900 Low- <strong>and</strong> Medium-Voltage Circuits Serving<br />

Three-Phase Alternating Current Equipment;<br />

Circuit Breakers<br />

Each of the four protective features required by this Section must<br />

be provided for all underground low- <strong>and</strong> medium-voltage three-phase<br />

a.c. circuits with the exception of trailing cables, which must have<br />

short-circuit, undervoltage, <strong>and</strong> grounded-phase protection. Circuit<br />

breakers providing short-circuit protection for trailing cables<br />

shall be adjusted so as not to exceed the maximum allowable<br />

instantaneous settings specified under Section 75.601-1. Shortcircuit<br />

<strong>and</strong> overcurrent protection for circuits shall conform to the<br />

National Electrical Code, 1968. Charts listing sizes <strong>and</strong> proper<br />

overload <strong>and</strong> short-circuit protection for motors <strong>and</strong> motor circuit<br />

conductors can be found in Appendix E of this volume. These tables<br />

shall be used to determine compliance with this Section.<br />

"Adequate interrupting capacity" is the ability of a circuit breaker<br />

to safely interrupt the maximum amount of current that can flow<br />

through its contacts upon occurrence of a short circuit at any point<br />

in the circuit without damage to itself.<br />

Low- <strong>and</strong> medium-voltage three-phase circuits used underground shall<br />

be protected against the harmful effects of a grounded phase in any<br />

circuit connected to the same transformer secondary. Consequently,<br />

if one bank of transformers supplies power to both underground <strong>and</strong><br />

surface loads, both the surface <strong>and</strong> underground portions of the<br />

circuit(s) shall be provided with grounded-phase protection.<br />

Grounded-phase protective devices for resistance-grounded circuits<br />

should be adjusted to operate on as low a value of fault current as<br />

practical, preferably not more than 50 percent of the current rating<br />

of the neutral grounding resistor.<br />

75.901 Protection of Low- <strong>and</strong> Medium-Voltage Three-Phase<br />

Circuits Used Underground<br />

When two phase conductors of a three-phase resistance grounded<br />

circuit are used to power single-phase loads, the equipment frames<br />

must be grounded to the grounded side of the grounding resistor.<br />

The grounding circuit shall be provided with a ground check circuit<br />

as required by Section 75.902 <strong>and</strong> the circuit shall be protected in<br />

accordance with the requirements of Section 75.900.<br />

February 2003 (Release V-33) 81

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!