MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />
Tapes or other materials that are used to form the outer jacket<br />
of approved permanent splices may be used to replace damaged<br />
areas of outer jackets of trailing cable. Outer jackets shall be<br />
replaced in such manner so as to prevent moisture from entering<br />
the cable.<br />
Tar-impregnated friction tape is not adequate for insulation or<br />
protection in the damp <strong>and</strong> wet areas of underground coal mines.<br />
Such tape will absorb mine water, which is highly conductive,<br />
creating a serious shock hazard to the miners.<br />
75.518-1 Electric Equipment <strong>and</strong> Circuits; Overload <strong>and</strong><br />
Short Circuit Protection; Minimum Requirements<br />
In direct-current systems that are either ungrounded or provided<br />
with a neutral grounding point, protective elements shall be<br />
provided for both positive <strong>and</strong> negative lines. This necessitates<br />
the use of either a two-pole circuit breaker or a fuse in each<br />
polarity. Fuses of the correct type <strong>and</strong> capacity are acceptable<br />
as overload protection only for d.c. or single-phase a.c.<br />
circuits <strong>and</strong> motors. The proper selection is based on wire size,<br />
motor design, horsepower, <strong>and</strong> method of starting. If the<br />
computed value is other than a common size, the next higher size<br />
common fuse or thermal element is acceptable.<br />
The installation of overload devices on locomotives operating on<br />
grades exceeding 5 percent can create a hazardous condition due<br />
to a decrease in braking power if the overcurrent protective<br />
devices open. Noncompliance with this Section shall not be cited<br />
for locomotives operating on grades exceeding 5 percent until<br />
suitable automatic brakes have been designed <strong>and</strong> installed on<br />
such locomotives <strong>and</strong> haulage cars.<br />
75.518-2 Inc<strong>and</strong>escent Lamps, Overload, <strong>and</strong> Short-Circuit<br />
Protection<br />
Not more than 8 feet in distance means not more than 8 feet of<br />
ungrounded conductor.<br />
75.519-1 Main Power Circuits; Disconnecting Switches;<br />
Locations<br />
This Section applies to low- <strong>and</strong> medium-voltage power circuits<br />
entering a mine <strong>and</strong> to low-, medium-, <strong>and</strong> high-voltage power<br />
circuits at the bottom of shafts <strong>and</strong> boreholes. The requirements<br />
for disconnecting switches for high-voltage power circuits<br />
entering a mine are contained in Section 75.802(c).<br />
February 2003 (Release V-33) 66