MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />

Subpart H Grounding<br />

77.700-1 Approved Methods of Grounding<br />

Approved methods of grounding the metallic enclosures of electric<br />

equipment receiving power from ungrounded alternating-current<br />

power systems are contained in Section 77.701-1.<br />

Approved methods of grounding the metallic enclosures of electric<br />

equipment powered from direct-current power systems are contained<br />

in Section 77.701-2.<br />

Subpart H does not specify approved methods of grounding the<br />

metallic enclosures of stationary equipment receiving power from<br />

low- <strong>and</strong> medium-voltage, solidly grounded alternating-current<br />

systems. Nevertheless, Section 77.701 requires that such<br />

enclosures be grounded by methods approved by an authorized<br />

representative of the Secretary. An inspector shall not approve<br />

any method of grounding that does not include a solid connection<br />

to a grounding conductor which extends to the grounded point of<br />

the power source. The grounded power conductor of a solidly<br />

grounded alternating-current power system may serve as the<br />

equipment grounding conductor only between the grounded point of<br />

the power source <strong>and</strong> the grounded enclosure of the service<br />

disconnecting means for a building or other stationary facility.<br />

The grounded point of the power source <strong>and</strong> the metallic enclosure<br />

of each service disconnecting means shall be connected to an<br />

acceptable grounding medium such as metal waterlines having lowresistance<br />

to earth, a low-resistance ground field, etc.<br />

Subpart H does not specify approved methods of grounding the<br />

metallic enclosures of portable or mobile equipment receiving<br />

power from high-voltage systems since the requirements for<br />

grounding such enclosures are specifically contained in Section<br />

77.802.<br />

This Section specifies approved methods of grounding metallic<br />

sheaths, armors <strong>and</strong> conduits enclosing power conductors. The<br />

approved methods of grounding listed in this Section are similar<br />

in that they each require a solid connection to an acceptable<br />

grounding medium. In resistance-grounded systems, the only<br />

acceptable grounding medium is the grounded neutral of the system.<br />

In other systems, an acceptable ground medium includes:<br />

1. Metal waterlines having low-resistance to earth;<br />

2. A low-resistance ground field; or<br />

3. Any other grounding medium which ensures that there is no<br />

difference in potential between the metallic enclosures<br />

February 2003 (Release V-33) 185