MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />

cable is compatible with the control unit <strong>and</strong> other components<br />

of the system.<br />

The assistance of a coal mine inspector (electrical) or electrical<br />

engineer should be requested, when necessary, to determine if a<br />

mine operator has installed heat sensors or heat sensor cables<br />

with opposite conductor color codes within a polarized fire sensor<br />

<strong>and</strong> warning device system.<br />

Other sensors addressed in paragraph (a)(2) that respond to<br />

effects of fire other than heat may be acceptable subject to<br />

individual determination. The Technical Support Group, in<br />

Bruceton, Pennsylvania, will provide assistance where needed in<br />

making this determination.<br />

"Unplanned removal of power" <strong>and</strong> "preplanned removal of power"<br />

referred to in paragraphs (a)(3) <strong>and</strong> (e) do not include those<br />

times when it is necessary to remove the power to make minor<br />

repairs or adjustments. An examination is not required for that<br />

period of time normally required for shift change, provided the<br />

time required for shift change does not exceed 2 hours.<br />

Where the operator chooses to make the examinations referred to in<br />

lieu of an automatic fire sensor <strong>and</strong> warning device system that<br />

will provide the 4-hour protection, the examination referred to<br />

would be required if the power supply to the sensor <strong>and</strong> alarm is<br />

removed, or the power is removed from the belt for more than 30<br />

minutes during a production shift, or the belt is stopped prior to<br />

the beginning of an idle shift or an idle period such as weekends<br />

or holidays.<br />

A battery must be disconnected automatically from the sensor<br />

system in the event the power is cut off as required by Section<br />

75.321, unless the sensor system is intrinsically safe.<br />

75.1103-5 Automatic Fire Warning Devices; <strong>Manual</strong> Resetting<br />

"Effective warning signal" as used in paragraph (a) of this<br />

Section means "a signal indicating an emergency <strong>and</strong> requiring<br />

immediate action." Both audible <strong>and</strong> visual signals shall be<br />

provided as required by Section 75.1103-1.<br />

The audible signal shall be capable of being heard from any point<br />

within the full range of the assigned duty locations of the person<br />

referred to in paragraphs (a)(1) <strong>and</strong> (a)(2), <strong>and</strong> the signal shall<br />

be audible above the normal sounds of the mining operation. This<br />

Section should be used to cite a failure of the system, when<br />

activated, when it does not provide an effective warning signal at<br />

either the work locations where miners may be endangered from a<br />

October 2003 (Release V-34) 106