05.06.2013 Views

Program Policy Manual - VOLUME V - Mine Safety and Health ...

Program Policy Manual - VOLUME V - Mine Safety and Health ...

Program Policy Manual - VOLUME V - Mine Safety and Health ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />

Subpart I Underground High-Voltage Distribution<br />

75.800 High-Voltage Circuits; Circuit Breakers<br />

A suitable circuit breaker is one that is:<br />

1. Capable of interrupting the maximum fault current to<br />

which it may be subjected without damage to itself;<br />

2. Capable of carrying the continuous current imposed upon<br />

it without damage to itself; <strong>and</strong><br />

3. Rated for not less than the voltage of the circuit.<br />

"Undervoltage protection" is defined in the IEEE St<strong>and</strong>ard<br />

Dictionary of Electrical <strong>and</strong> Electronic Terms (IEEE St<strong>and</strong>ards 100-<br />

1972) as "the effect of a device, operative on the reduction or<br />

failure of voltage, to cause <strong>and</strong> maintain the interruption of<br />

power to the main circuit." The principal purpose for<br />

undervoltage protection is to prevent automatic restarting of<br />

equipment when power is restored after an outage. Undervoltage<br />

protection can be provided by an undervoltage trip coil on the<br />

circuit breaker or by an undervoltage relay or a ground-check<br />

relay connected into the circuit breaker trip circuit. When an<br />

undervoltage relay or ground-check relay is used to operate the<br />

shunt trip coil on a circuit breaker, a stored-energy tripping<br />

source must be provided (i.e., capacitor trip or battery trip) to<br />

insure that the circuit breaker will trip during a power outage.<br />

The undervoltage relay may either be an induction or attraction<br />

type <strong>and</strong> must trip the circuit breaker when the line voltage<br />

decreases to 40 percent of nominal or less when power is lost.<br />

A high-voltage circuit extending underground shall be protected<br />

against the harmful effects of a grounded phase in the underground<br />

circuit <strong>and</strong> in any surface circuit supplied from the same set of<br />

transformer windings. Consequently, if one set of transformer<br />

windings supplies resistance-grounded power to both underground<br />

<strong>and</strong> surface loads, the circuit(s) extending to the surface loads<br />

must also be provided with grounded-phase protection. Fuses may<br />

be used to provide grounded-phase protection only for small<br />

control transformers installed in the same substation as the<br />

transformers that supply the resistance- grounded circuit. In all<br />

other cases, circuit breakers equipped with grounded-phase<br />

protective devices must be used to provide the required groundedphase<br />

protection.<br />

Grounded-phase relays should be adjusted to operate on as low a<br />

value of current or voltage as practical. In order to provide<br />

safe, reliable relaying, settings should not exceed 50 percent of<br />

the maximum fault current for current relaying or 50 percent of<br />

February 2003 (Release V-33) 74

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!