MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />

Subpart I Surface High-Voltage Distribution<br />

77.800 High-Voltage Circuits; Circuit Breakers<br />

High-voltage circuits supplying power to portable or mobile<br />

alternating-current equipment shall be protected against the<br />

harmful effects of a grounded phase in any circuit connected to<br />

the same transformer secondary. Consequently, if one bank of<br />

transformers supplies power to both stationary <strong>and</strong> portable or<br />

mobile loads, the circuit(s) extending to the stationary loads,<br />

as well as the circuit(s) extending to the portable or mobile<br />

loads, shall be provided with grounded phase protection.<br />

Grounded phase protection for resistance-grounded circuits<br />

should be adjusted to operate on as low a value of fault<br />

current as practical; preferably not more than 40 percent of<br />

the current rating of the neutral grounding resistor.<br />

77.800-1 Testing, Examination, <strong>and</strong> Maintenance of Circuit<br />

Breakers; Procedures<br />

Paragraph (c) does not require the tank surrounding the oil<br />

circuit breakers to be dropped during this examination unless<br />

there is doubt of the qualified person making this examination<br />

as to conditions inside the tank.<br />

77.802 Protection of High-Voltage Circuits; Neutral<br />

Grounding Resistors; Disconnecting Devices<br />

The exception in this Section applies to high-voltage systems<br />

which supply power to stationary surface equipment only.<br />

Consequently, if a high-voltage system supplies power to<br />

equipment located underground in a mine, as well as equipment<br />

located on the surface, the frames of all equipment supplied<br />

power from the system shall be grounded in accordance with<br />

Section 75.802. Likewise, if a high-voltage system supplies<br />

power to portable or mobile equipment located on the surface,<br />

as well as stationary equipment located on the surface, the<br />

frames of all equipment supplied power from the system shall be<br />

grounded in accordance with the resistance grounding<br />

requirements of this Section.<br />

77.803 Fail Safe Ground Check Circuits on High-Voltage<br />

Resistance-Grounded Systems<br />

The ground check circuit required by this Section shall cause<br />

the circuit breaker to trip when any of the following occur:<br />

1. The ground check wire is broken; <strong>and</strong><br />

February 2003 (Release V-33) 189