MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />

2. Secondary injection test. This test method involves<br />

passing sufficient current to cause the circuit breaker<br />

to trip through at least two of the protective relays<br />

associated with the circuit breaker.<br />

This method simultaneously tests the operation <strong>and</strong><br />

calibration of relays <strong>and</strong> the operation of the circuit<br />

breaker trip circuit.<br />

3. Mechanical activation test. This test method involves<br />

mechanically activating at least two of the protective<br />

relays associated with the circuit breaker with a non-<br />

conductive probe. This method tests the operation of<br />

the circuit breaker trip circuit.<br />

75.801 Grounding Resistors<br />

Grounding resistors that are manufactured to meet the extended<br />

time rating as set forth in IEEE St<strong>and</strong>ard 32-1972, formerly AIEE<br />

St<strong>and</strong>ard 32, are acceptable as compliance with this Section.<br />

Resistors that are not manufactured in compliance with IEEE<br />

St<strong>and</strong>ard 32-1972 shall be "rated for maximum fault current<br />

continuously."<br />

75.802 Protection of High-Voltage Circuits Extending<br />

Underground<br />

Grounding transformers must be sized to carry the rated groundfault<br />

current of the system continuously. Consequently, the kVA<br />

rating of a zigzag grounding transformer or a wye-delta grounding<br />

transformer bank shall not be less than the rated phase-to-neutral<br />

voltage of the system (VON) in kV times the rated ground-fault<br />

current of the system (I) in amperes. If other loads are supplied<br />

from a wye-delta grounding transformer bank, the rating of the<br />

transformer bank must be adequate to supply the additional loads<br />

plus the rated ground-fault current.<br />

Transformer banks connected wye on the primary side <strong>and</strong> supplied<br />

power from a resistance-grounded circuit shall not have the<br />

primary neutral grounded.<br />

When used, grounding transformers shall be connected on the line<br />

side of circuit breakers so that the system will always be<br />

grounded <strong>and</strong> must be located in/or adjacent to the same substation<br />

as the power source transformers.<br />

This Section requires that the grounding resistor be located at<br />

the source transformers. As used in this Section, the term<br />

"source transformer" means the transformer that supplies power to<br />

the electric circuit.<br />

JULY 2006 (Release V-38) 76