MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />
2. Secondary injection test. This test method involves<br />
passing sufficient current to cause the circuit breaker<br />
to trip through at least two of the protective relays<br />
associated with the circuit breaker.<br />
This method simultaneously tests the operation <strong>and</strong><br />
calibration of relays <strong>and</strong> the operation of the circuit<br />
breaker trip circuit.<br />
3. Mechanical activation test. This test method involves<br />
mechanically activating at least two of the protective<br />
relays associated with the circuit breaker with a non-<br />
conductive probe. This method tests the operation of<br />
the circuit breaker trip circuit.<br />
75.801 Grounding Resistors<br />
Grounding resistors that are manufactured to meet the extended<br />
time rating as set forth in IEEE St<strong>and</strong>ard 32-1972, formerly AIEE<br />
St<strong>and</strong>ard 32, are acceptable as compliance with this Section.<br />
Resistors that are not manufactured in compliance with IEEE<br />
St<strong>and</strong>ard 32-1972 shall be "rated for maximum fault current<br />
continuously."<br />
75.802 Protection of High-Voltage Circuits Extending<br />
Underground<br />
Grounding transformers must be sized to carry the rated groundfault<br />
current of the system continuously. Consequently, the kVA<br />
rating of a zigzag grounding transformer or a wye-delta grounding<br />
transformer bank shall not be less than the rated phase-to-neutral<br />
voltage of the system (VON) in kV times the rated ground-fault<br />
current of the system (I) in amperes. If other loads are supplied<br />
from a wye-delta grounding transformer bank, the rating of the<br />
transformer bank must be adequate to supply the additional loads<br />
plus the rated ground-fault current.<br />
Transformer banks connected wye on the primary side <strong>and</strong> supplied<br />
power from a resistance-grounded circuit shall not have the<br />
primary neutral grounded.<br />
When used, grounding transformers shall be connected on the line<br />
side of circuit breakers so that the system will always be<br />
grounded <strong>and</strong> must be located in/or adjacent to the same substation<br />
as the power source transformers.<br />
This Section requires that the grounding resistor be located at<br />
the source transformers. As used in this Section, the term<br />
"source transformer" means the transformer that supplies power to<br />
the electric circuit.<br />
JULY 2006 (Release V-38) 76