MSHA PROGRAM POLICY MANUAL <strong>VOLUME</strong> V<br />
The figures "50 feet" <strong>and</strong> "150 feet" referred to in Sections<br />
75.1101, 75.1101-5(b)(1) <strong>and</strong> (2), 75.1101-7(b) <strong>and</strong> 75.1101-14(a)<br />
mean lineal feet of belt entry.<br />
Guidelines for Fire Protection at Surface Located Drive Units for<br />
Underground Belt Conveyors:<br />
1. All belt drive units located within 25 feet of any intake<br />
airway should be equipped with an automatically actuated<br />
fire suppression system as described in this Section.<br />
2. Belt drive units located more than 25 feet but less than<br />
50 feet from any intake airway should be equipped with an<br />
automatically actuated fire suppression system, unless<br />
fire doors or air lock doors are provided in the belt<br />
entry <strong>and</strong> in all intake entries within 50 feet of the<br />
drive unit.<br />
3. Belt drive units located more than 50 feet but less than<br />
100 feet from any intake airway should be equipped with a<br />
sensor system which will automatically sound an alarm <strong>and</strong><br />
stop the conveyor drive motor when a fire occurs on or<br />
near such belt drive.<br />
The alarm shall be at a location where it can be heard by<br />
a responsible person who is always on duty while men are<br />
underground.<br />
If a responsible person is not stationed where he can hear<br />
the alarm <strong>and</strong>/or is not always on duty while the belt is<br />
running <strong>and</strong> miners are underground, a fire door or air<br />
lock should be installed in the belt entry <strong>and</strong> all intake<br />
entries within 100 feet of the belt drive. If the<br />
conditions are not met, a fire suppression system should<br />
be required.<br />
4. Belt drive units located 100 feet or more from any intake<br />
airway should be protected with one or two portable fire<br />
extinguishers as applicable under Sections 75.1100-2(e)(1)<br />
or (e)(2) (electrical installations).<br />
Measurements made to determine the distance between the<br />
drive unit <strong>and</strong> the mine opening should be made between the<br />
belt drive roller <strong>and</strong> the nearest mine opening or intake<br />
airway, as applicable. The fire suppression system, fire<br />
door/air lock doors, <strong>and</strong> sensor controlled stop <strong>and</strong> alarm<br />
described in paragraphs 1, 2, 3 <strong>and</strong> 4 are in addition to<br />
October 2003 (Release V-34) 98