6.8.7 Raw input overview<br />

Measured temperatures, input status and voltages are displayed.<br />

In addition, a detection of malfunctions can be chosen for activated<br />

temperature inputs.<br />

Monitoring the sensors:<br />

Choose the sensor which measures a temperature, for example the<br />

S5. When the dial is pressed, a magnifying glass appears in the<br />

selected line. The S5 temperature is now being monitored.<br />

Alarm indication:<br />

Should the connection to the temperature sensor be disconnected,<br />

short-circuited or the sensor itself be defective, the alarm function<br />

is activated.<br />

In the "Raw input overview" an alarm symbol is shown at the<br />

defective temperature sensor in question.<br />

Resetting the alarm:<br />

Choose the sensor (S number) for which you want to clear the<br />

alarm. Press the dial. The magnifying glass and alarm symbols<br />

disappear.<br />

When the dial is pressed again, the monitoring function is<br />

reactivated.<br />

6.8.8 Display<br />

Backlight (display brightness) 60058<br />

Circuit Setting range Factory setting<br />

Adjust the brightness of the display.<br />

0: Weak backlight.<br />

10: Strong backlight.<br />

0 ... 10 5<br />

Contrast (display contrast) 60059<br />

Circuit Setting range Factory setting<br />

Adjust the contrast of the display.<br />

0: Low contrast.<br />

10: High contrast.<br />

0 ... 10 3<br />

The temperature sensor inputs have a measuring range from -60 ...<br />

150 ° C.<br />

If a temperature sensor or its connection breaks, the value indication<br />

is " - - ".<br />

If a temperature sensor or its connection is short-circuited, the value<br />

indication is " - - - ".<br />