<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />

Stop difference - <strong>A217</strong>.1 / <strong>A217</strong>.2 / <strong>A317</strong>.1 / <strong>A317</strong>.2 11194<br />

Circuit Setting range Factory setting<br />

1 –50 ... 50 K 3 K<br />

One DHW tank temperature sensor:<br />

Set the number of degrees above the desired DHW temperature that will<br />

stop the DHW heating (charging).<br />

Two DHW tank temperature sensors:<br />

Set the number of degrees above or below the desired DHW temperature<br />

but measured by the lower tank temperature sensor that will stop the DHW<br />

heating (charging).<br />

–50 ... 50: Set the number of degrees.<br />

One DHW tank temperature sensor (example with positive ‘Stop<br />

difference’ value):<br />

Temp.<br />

° C<br />

DHW heating<br />

Stop difference<br />

Desired DHW temp.<br />

Time<br />

One DHW tank temperature sensor (example with negative ‘Stop<br />

difference’ value):<br />

Temp.<br />

° C<br />

DHW heating<br />

Stop difference<br />

Desired DHW temp.<br />

Time<br />

Two DHW tank temperature sensors, upper and lower<br />

Temp.<br />

° C<br />

DHW heating<br />

Upper DHW temp. sensor<br />

Stop difference<br />

Desired DHW temp.<br />

Lower DHW temp. sensor<br />

74 DEN-SMT/DK VI.LG.U2.02 <strong>Danfoss</strong> District Energy<br />