<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A217</strong> / <strong>A317</strong><br />
The return temperature (S5) to the district heating supply should<br />
not be too high. If so, the desired charging temperature can be<br />
adjusted (typically to a lower value), thus resulting in a gradual<br />
closing of the motorized control valve.<br />
In boiler-based heating supply the return temperature should not<br />
be too low (same adjustment procedure as above).<br />
The supply temperature, S2, is used for adjusting the proportional<br />
band (Xp) in order to give a stable temperature control.<br />
An anti-bacteria function is available for activation on selected<br />
days of the week.<br />
The outdoor temperature sensor S1 is used to protect the<br />
circulation circuit against frost.<br />
The DHW circulation pump (P3) has a week schedule for up to 3<br />
ON-periods per day.<br />
Application <strong>A217</strong>.2 (used in <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong>) / <strong>A317</strong>.2 (used in<br />
<strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong>) in general:<br />
A Remote Control Unit, the ECA 30, can be connected in order to<br />
control the <strong>ECL</strong> controller remotely.<br />
A connected flow or energy meter (in <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> it is based<br />
on pulse signals and in <strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong> based on M-bus signal)<br />
can limit the flow or energy to a set maximum.<br />
Unused input can, by means of an override switch, be used to<br />
override the schedule to a fixed '<strong>Comfort</strong>' or 'Saving' mode.<br />
Modbus communication to a SCADA system can be established. In<br />
<strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong> the M-bus data can furthermore be transferred<br />
to the Modbus communication.<br />
Alarm relay (in <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> it is R4 and in <strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong> R6)<br />
can be activated if the actual flow temperature at S3 differs from<br />
the desired DHW heating temperature.<br />
<strong>A217</strong>.2 / <strong>A317</strong>.2 example a:<br />
S1<br />
S2 S3<br />
M1<br />
S5<br />
P1<br />
<strong>A217</strong>.2 / <strong>A317</strong>.2 example b:<br />
S1<br />
M1<br />
S2 S3<br />
<strong>ECL</strong> <strong>210</strong> / (<strong>310</strong>)<br />
S4<br />
B<br />
P2<br />
<strong>ECL</strong> <strong>210</strong> / (<strong>310</strong>)<br />
<strong>Danfoss</strong> District Energy VI.LG.U2.02 DEN-SMT/DK 7<br />
S5<br />
P1<br />
S4<br />
B<br />
P2<br />
A1<br />
A1<br />
S6<br />
A<br />
S8<br />
S6<br />
A<br />
S8<br />
P3<br />
P3<br />
<strong>Danfoss</strong><br />
87H2071.11<br />
<strong>Danfoss</strong><br />
87H2072.11